Inspections for the day of: Friday, June 7, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01520 Final6/7/20196/7/20196/7/2019 2:57:35 PMPPASS
Gfci recaps installed ready for re inspection Phone #: ###-#### Inspection requested via web by Kevin Oderkirk Final ok
ELE19-01406 Electrical Rough-In6/7/20196/7/20196/7/2019 2:22:35 PMPPASS
Contact John Mittlieder for Level 1 A1 walls. Level 2 bathroom ceilings and top out rough in. Phone #: ###-#### Inspection requested via web by Tom Betty
Level 1 A1 walls and level 2 A1 bathrooms and corridor fire lids and top out rough in ok cover
ELE19-00770 Final6/6/20196/7/20196/7/2019 1:25:40 PMPPART
Partial Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Shop, bull pen, break rm, conference rm, 109, 110 and reception area TCO ok
ELE19-00797 Final6/6/20196/7/20196/7/2019 12:04:55 PMAPASS
Inspection requested via web by BRS Permitting Final ok
ELE19-01890 Electrical Rough-In6/6/20196/7/20196/7/2019 12:04:29 PMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Level 1 bathrooms rough in ok cover
ELE19-01984 Final6/5/20196/7/20196/7/2019 11:20:03 AMAPASS
final on hot tub inspection that needed a new plastic fixture installed. fixture has been replaced and picture sent to Darrell Phone #: ###-#### Inspection requested via web by A.M.E. Office
As per Daryl DeGrange he has notes of item in question. Final ok
ELE19-00930 Final6/6/20196/7/20196/7/2019 11:18:53 AMAFAIL
Garage Code 4053 Phone #: ###-#### Inspection requested via web by Dean Gernaat
314.16- Boxes shall be of sufficient size for all conductors installed. 8 cubic inch box installed for island receptacle 11.25 cubic inches of conductor installed.
* Fee charged is for service up to 200 amp only $55.00. Fee for dwelling required. Additional $80.00 total of $135.00 required.
ELE18-03224 Permanent Service6/6/20196/7/20196/7/2019 10:08:48 AMACANC
Contact: Wes powell Phone #: ###-#### Inspection requested via web by Deb Gooden
Needed rough in inspection.
ELE18-03224 Electrical Rough-In6/7/20196/7/20196/7/2019 10:08:31 AMPPASS
Contact: Wes powell Phone #: ###-#### Inspection requested via web by Deb Gooden
Inspect old service gear located in existing portion of school now sub fed from new service. Rough in ok
ELE19-01648 Final6/6/20196/7/20196/7/2019 9:30:31 AMAFAIL
Final inspection. Phone #: ###-#### Inspection requested via web by David Feller
See ceiling rough in inpection.
ELE19-01648 Rough-In Permanent Service6/6/20196/7/20196/7/2019 9:29:59 AMAFAIL
Ceiling cover inspection. Phone #: ###-#### Inspection requested via web by David Feller
210.8- All 15 and 20 amp 120 volt receptacle outlets located with in 6' of a sink shall have GFCI protection. Break room.
314.25- All boxes shall have covers. Reception and waiting areas.
*BLD19-01289 lists break room as being created under this permit and shall be part of scope of work.