Inspections for the day of: Friday, July 12, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02588 Permanent Service7/12/20197/12/20197/12/2019 2:37:36 PMPNH
Space is been empty for three or four years need to get inspection so meter can be set. Please call Nicole with Colliers in advance. 208 -###-####. Located in Hampton in building south of parking garage entry. Please call with any questions Phone #: ###-#### Inspection requested via web by Rex Boyles
Called Nicole 20 minutes prior to arrival, no answer, left message, door locked, contractor directed me to electrical room which was also locked. Will recall when accessible.
ELE19-02574 Electrical Rough-In7/11/20197/12/20197/12/2019 1:59:18 PMPPASS
Phone #: ###-#### Inspection requested via web by sam petterson
Addition to front and rear of garage with rewire old garage area. Rough in ok cover
ELE19-02556 Rough-In Permanent Service7/10/20197/12/20197/12/2019 1:17:51 PMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk
Rough in ok cover p/s u/g rec ok
ELE19-01804 Final7/11/20197/12/20197/12/2019 12:49:46 PMAPASS
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
ELE19-01527 Final7/12/20197/12/20197/12/2019 11:56:38 AMPFAIL
garage code 7530 Phone #: ###-#### Inspection requested via web by Darryn Coburn 110.3- Devices shall be wired as per manufacturers instructions. Christmas GFCI will not set, Bath GFCI hot load is not hot.
110.7- Finished product shall be free of short circuits. Garage circuit breaker trips when GFCI is set.
314.25- All boxes shall have covers. Up niche light box open.
ELE19-01199 Final7/11/20197/12/20197/12/2019 11:52:21 AMAPASS
garage code 7530 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
ELE19-02573 Conference7/11/20197/12/20197/12/2019 10:20:40 AMAPASS
Scott Phone #: ###-####
Discussed refeeding existing AC unit from existing disconnect underground. concrete will cover this area, sch 80, depth, conductors. pamphlet given
ELE19-01406 Electrical Rough-In7/11/20197/12/20197/12/2019 9:29:16 AMAPASS
4 level 1 kitchen pony walls and level 1 area B lids. Phone #: ###-#### Inspection requested via web by Tom Betty
Level 1 area B not ready. Kitchen and breakroom changes in walls rough in ok cover
ELE19-01604 Final7/12/20197/12/20197/12/2019 9:09:53 AMAPASS
Phone #: ###-#### Inspection requested via web by Bryan McLaughlin Final ok
ELE19-01317 Final7/11/20197/12/20197/12/2019 8:52:02 AMAPASS
Contact: Ryan Mrachek Phone #: ###-#### Inspection requested via web by Deb Gooden Final ok