Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01329 ELE-Aging Inspection7/15/20167/15/20167/15/2016 3:04:01 PM CANC
ELE10-00275 ELE-Aging Inspection7/15/20167/15/20167/15/2016 3:03:42 PM CANC
ELE10-00196 ELE-Aging Inspection7/15/20167/15/20167/15/2016 3:03:35 PM CANC
ELE16-02264 Electrical Rough-In7/15/20167/15/20167/15/2016 3:02:59 PMPPASS
Bathroom wire Phone #: ###-#### Inspection requested via web by Greg Idsinga
Bathroom walls and hardlid rough in ok cover
ELE16-02161 Electrical Rough-In7/15/20167/15/20167/15/2016 2:39:29 PMPPASS
If you have any questions, please call Jared ###-####. Thank You! Phone #: ###-#### Inspection requested via web by Clay Morgan
Called to attach to BLD16-01557. Unit 2277 rough in ok cover
ELE16-02160 Electrical Rough-In7/15/20167/15/20167/15/2016 2:39:12 PMPPASS
If you have any questions, please call Jared ###-####. Thank You! Phone #: ###-#### Inspection requested via web by Clay Morgan
Called to attach to BLD16-01557. Unit 2275 rough in ok cover
ELE15-03901 Electrical Rough-In7/15/20167/15/20167/15/2016 2:10:33 PMPPASS
Call for r/i inspection of cabinet wall on 8th floor east break room. Phone #: ###-#### Inspection requested via web by Rafael Castillo
As noted rough in ok cover
ELE15-01617 Electrical Rough-In7/14/20167/15/20167/15/2016 1:19:52 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Underground in planters in south parking lot rough in ok cover
ELE15-02740 Conference7/15/20167/15/20167/15/2016 12:52:50 PMPDONE
Thac Phone #: ###-####090
Discusses the access to disconnecting means of HVAC equipment and duct heaters. As per Daryl DeGrange need 24" deep if possible in no case access be less than 18".
ELE16-01667 Conference7/14/20167/15/20167/15/2016 11:09:26 AMAPASS
Discuss use of romex in all condo''s with Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Discussed use of NM cable in condos. Building permit noted type V construction. NM cable shall have at least 15 minute fire barrier and not be installed above drop or grid ceilings as per NEC 334.10. Also mentioned access to HVAC unit control boxes shall have room to access.
ELE16-01964 Final7/14/20167/15/20167/15/2016 10:09:38 AMAPASS
Swimming Pool - Shon Phone #: ###-#### Corrections made. Final ok
ELE16-01846 Final7/14/20167/15/20167/15/2016 9:32:18 AMAPASS
If you have any questions please call Mike ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
ELE16-02256 Electrical Rough-In7/14/20167/15/20167/15/2016 9:13:46 AMAPASS
Brandon is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
11 of 14 west, south and east pole bases. Underground installed prior to inspection. All U/G under sidewalk and planter areas. rough in ok cover
ELE16-01867 Final7/14/20167/15/20167/15/2016 8:59:32 AMAPASS
Phone #: ###-#### Inspection requested via web by Tracy Robertson
As per Daryl Degrange show window receptacles OK'd above 18" at rough in stage. Final ok