ELE19-02688
| Electrical Rough-In | 7/19/2019 | 7/19/2019 | 7/19/2019 2:41:41 PM | P | PART |
|
|
New Wall Rough-in only Phone #: ###-#### Inspection requested via web by Kevin Perez Eastern training rm and small conference rm walls not built yet, rest of walls only rough in ok cover.
|
ELE19-02484
| Rough-In Permanent Service | 7/19/2019 | 7/19/2019 | 7/19/2019 2:19:56 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Same Electric Service only, at time of inspection still removing old panel, ground rods driven, and meter base mounted. Due to a Friday inspection and work being performed by licensed contractor will approve without all being completed. At time of final need to remove cover and inspect all terminations. Materials on site all correct. p/s u/g rec ok
|
ELE19-00444
| Final | 7/18/2019 | 7/19/2019 | 7/19/2019 1:18:55 PM | P | PASS |
|
|
Please call the homeowner on your way there. Phil McClain ###-####. Thanks Phone #: ###-#### Inspection requested via web by Barbara Szurgot Final ok
|
ELE19-01406
| Electrical Rough-In | 7/17/2019 | 7/19/2019 | 7/19/2019 12:22:04 PM | A | PASS |
|
|
A155, B104, 105,106,118,122,123,162 Phone #: ###-#### Inspection requested via web by Tom Betty Areas noted with addition of area B corridor walls and lids rough in ok cover
|
ELE19-02649
| Permanent Service | 7/17/2019 | 7/19/2019 | 7/19/2019 10:49:26 AM | A | PASS |
|
|
Joe Kaminsky is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Grounding electrodes located in base of light pole and ground box to West of pole, labels complete. Informed could not final until energized. Will request final when ready. p/s u/g n ok
|
ELE19-00850
| Final | 7/19/2019 | 7/19/2019 | 7/19/2019 10:38:56 AM | A | PASS |
|
|
Garage code 0813 Phone #: ###-#### Inspection requested via web by cal crosby Final ok
|
ELE19-01935
| Final | 7/18/2019 | 7/19/2019 | 7/19/2019 10:18:10 AM | A | FAIL |
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Icon Electric 408.4- Circuit directory shall be complete and accurate. Lock out on wrong breaker. Complete directory.
|
ELE19-00604
| Final | 7/18/2019 | 7/19/2019 | 7/19/2019 9:41:00 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Final ok
|
ELE19-00604
| Electrical Rough-In | 7/19/2019 | 7/19/2019 | 7/19/2019 9:40:44 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Disconnect and listing confirmed. Rough in ok
|
ELE19-02634
| Temporary Service | 7/18/2019 | 7/19/2019 | 7/19/2019 8:39:27 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by David Nelson t/s u/g n ok
|