Inspections for the day of: Thursday, July 23, 2020.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-02565 Permanent Service7/23/20207/23/20207/23/2020 2:40:31 PMPPASS
repaired mast on 200amp overhead service Phone #: ###-#### Inspection requested via web by Kendra Lanham Mast only replaced. p/s o/h rec ok
ELE20-01794 Electrical Rough-In7/23/20207/23/20207/23/2020 1:44:30 PMPPASS
Ceiling cover Phone #: ###-#### Inspection requested via web by Shane Lott Asked if grid in clean room over assembly table could be covered, explained would need a tile left out so inspector could verify boxes in this area and wiring method to plug mold used comply with code. Partilal grid for clean room, west office space and 2 west hallways grid rough in ok cover.
ELE19-04696 Final7/23/20207/23/20207/23/2020 10:52:06 AMAPASS
Final is for Cabana only. We did not do the pool electrical. Thank you! Phone #: ###-#### Inspection requested via web by Eric Brown Final ok
ELE19-03624 Electrical Rough-In7/22/20207/23/20207/23/2020 10:17:43 AMAPASS
Ceiling Inspection for the Powder Room in Unit #506.
Contact electrician Alex Ybarra for any questions.
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Powder bath ceiling only rough in ok cover.
ELE20-01496 Final7/22/20207/23/20207/23/2020 9:42:29 AMAPASS
garage code 4224 Phone #: ###-#### Inspection requested via web by Troy Ballard Final ok
ELE20-02544 Temporary Service7/22/20207/23/20207/23/2020 9:18:05 AMAPASS
Phone #: ###-#### Inspection requested via web by Kevin Heideman t/s u/g n ok
ELE20-02546 Temporary Service7/22/20207/23/20207/23/2020 9:17:40 AMAPASS
Phone #: ###-#### Inspection requested via web by Kevin Heideman t/s u/g n ok
ELE20-02534 Temporary Service7/22/20207/23/20207/23/2020 9:15:40 AMAFAIL
Phone #: ###-#### Inspection requested via web by Angela Stears 250.53(G)- Ground rod shall be flush with or below grade.
ELE20-02535 Temporary Service7/22/20207/23/20207/23/2020 9:14:38 AMAFAIL
Phone #: ###-#### Inspection requested via web by Angela Stears 110.26- Minimum work space shall be provided for temp pole of 36" deep x 30" wide. Panel door hits transformer.