Inspections for the day of: Wednesday, July 24, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01088 Final7/24/20197/24/20197/24/2019 2:43:37 PMPFAIL
Phone #: ###-#### Inspection requested via web by Kevin Perez
110.3- A double duplex located in conference room not working.
210.63- A service 120 volt 15 or 20 amp receptacle shall be located with in 25' of AC unit. 314.23- Boxes shall be securely mounted. MC and boxes sitting on top of file cabinets.
314.25- 3 open boxes found in eastern open area shall have covers.
408.4- Panel 2 circuit directory shall be complete.
440.11- A disconnecting means shall be provided for newer AC unit.
*BCC 4-05-32- Code violations not to be retained. Checked all unoccupied areas.
ELE19-01406 Electrical Rough-In7/24/20197/24/20197/24/2019 1:45:03 PMPPASS
Cover inspection SW stairwell. Phone #: ###-#### Inspection requested via web by Tom Betty Level 2 publec bathroom ceilings, S.E. stairway soffit ok to build, and S.W. as noted rough in ok cover.
ELE19-01953 Final7/23/20197/24/20197/24/2019 11:35:19 AMAFAIL
Roof replacement is completed and electrical has been reconnected out of
2nd floor and stairwell panels for final. Please call with any questions as no contact is on site but could meet on site if needed. Phone #: ###-#### Inspection requested via web by Jim Noll
314.25- All boxes shall have covers. 12"x12" on roof, 4sq on stair to roof, level 2 bar 3 gang that controls level 2 lighting and receptacles.
GFCI receptacles installed around perimeter of roof parapet 2 are hot conatantly rest switched by contact and switch, no heat tape part of scope of work.
Also pending investigating the installation of 2 double duplex in level 2 ceiling added by others with no covers and 2 single gang receptacles has not installed ro have been removed by others.
ELE19-01398 Final7/22/20197/24/20197/24/2019 10:24:39 AMAPASS
Please call customer when arriving and wait a few minutes for him to call back-cell reception is bad in building ###-#### Phone #: ###-#### Inspection requested via web by Same Electric
Counter top not in, 2" thick granite planned.
Final ok.
ELE19-02735 Electrical Rough-In7/23/20197/24/20197/24/2019 9:40:07 AMAPASS
There are 2 permits for this job please make arrangements with me to coordinate with you so we can show you what we did and not interrupt customers. other permit number is ELE19-02733 Phone #: ###-#### Inspection requested via web by Rick Beckman
Small area wall rough in ok cover
ELE19-02733 Electrical Rough-In7/23/20197/24/20197/24/2019 9:19:40 AMAPASS
There are 2 permits for this job please make arrangements with me to coordinate with you so we can show you what we did and not interrupt customers. other permit number is ELE19-02735 Phone #: ###-#### Inspection requested via web by Rick Beckman
Small area, wall rough in ok cover
ELE19-02247 Electrical Rough-In7/23/20197/24/20197/23/2019 1:30:30 PMAPASS
Wall sign inspection Phone #: ###-#### Inspection requested via web by Ken Olsen
Change of plans, letters to mount directly to parapet with drivers to be installed in a box behind an access that is to be cut into parapet. Listings confirmed. Rough in ok