ELE19-02757
| Permanent Service | 7/25/2019 | 7/25/2019 | 7/25/2019 3:21:33 PM | P | PASS |
|
|
Service reconnect due pole fell over. New meter located on garage. p/s o/h rec ok
|
ELE19-02757
| Final | 7/24/2019 | 7/25/2019 | 7/25/2019 3:20:54 PM | A | PASS |
|
|
Please call me 30 min prior for access as it is gated so myself or the owner can meet! Thanks, Steve Phone #: ###-#### Inspection requested via web by Steven Meredith Labels complete. Final ok
|
ELE19-02670
| Electrical Rough-In | 7/25/2019 | 7/25/2019 | 7/25/2019 2:58:16 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Steven Ragan Grid rough in ok cover
|
ELE19-01018
| Final | 7/25/2019 | 7/25/2019 | 7/25/2019 2:29:22 PM | P | FAIL |
|
|
Final for pad 3 Phone #: ###-#### Inspection requested via web by Lee VanSchoiack 314.25- All boxes shall have covers. 3 located in ceiling above panel, 1 ceiling south side. 330.30- MC cable shall be secured with in 12" of a box. Several thru out. 590.6- All 15 and 20 amp 120 volt receptacle outlets installed for power during construction shall have GFCI protection for personel.
|
ELE19-01296
| Final | 7/24/2019 | 7/25/2019 | 7/25/2019 1:18:16 PM | P | PASS |
|
|
Please call Jim for access ###-#### Phone #: ###-#### Inspection requested via web by William Andrews Final ok
|
ELE19-01893
| Final | 7/24/2019 | 7/25/2019 | 7/25/2019 12:18:25 PM | A | PART |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Office 108 receptacles not working. Heat tape has been removed from scope of work. Circuit dtrectory shall be complete.
|
ELE19-01893
| Electrical Rough-In | 7/24/2019 | 7/25/2019 | 7/25/2019 11:43:41 AM | A | PASS |
|
|
Please call 30 mins prior to inspection Phone #: ###-#### Inspection requested via web by Kerri Hamilton Grid rough ok cover
|
ELE19-01917
| Final | 7/24/2019 | 7/25/2019 | 7/25/2019 10:50:38 AM | A | FAIL |
|
|
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn 210.70- Switch located at top and bottom of stair shall operate stair light. Miss wire, 1 switch locks out other.
|
ELE19-00030
| Electrical Rough-In | 7/24/2019 | 7/25/2019 | 7/25/2019 9:14:46 AM | A | PASS |
|
|
Partial rough-in inspection for the southeast corner of the showroom. Phone #: ###-#### Inspection requested via web by Bryan Atkins Area noted wall rough in ok cover
|