Inspections for the day of: Friday, July 29, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01914 ELE-Aging Inspection7/29/20167/29/20168/5/2016 2:30:38 PM PASS
Able to see disconnecting means think listing sticker painted over.
ELE15-03901 Final7/29/20167/29/20167/29/2016 3:11:20 PMPPART
Call Rafael for TCO for floors 6 and 7. Phone #: ###-#### Inspection requested via web by Rafael Castillo
temp final for stairways, corridors, egress floors 6 and 7
ELE16-02461 Conference7/29/20167/29/20167/29/2016 3:04:46 PMPDONE
Please call 30 minutes prior Phone #: ###-#### Inspection requested via web by John Edwards
Discussed the installation of an auxillary gutter on outside of building to intercept 2 conduits . Want to manufacture gutter af sufficient size
ELE16-01853 Final7/29/20167/29/20167/29/2016 1:47:25 PMPFAIL
Any questions please call, thx Phone #: ###-#### Inspection requested via web by Stephen Kren
110.3- Switch in up hall miss wire shall be connected as per manufacturers instructions.
110.22- label switches for furnace disconnects.
210.52- Receptacle outlets shall be installed for each basin in down bath.
ELE16-01890 Electrical Rough-In7/26/20167/29/20167/29/2016 12:33:55 PMPPASS
Equipoytential Phone #: ###-#### Inspection requested via web by Louis Keller
Perimeter bond rough in ok cover
ELE15-00495 Electrical Rough-In7/28/20167/29/20167/29/2016 11:43:06 AMAPASS
Ceiling rough in 1st floor. Service corridors. Contact is Toby Groves ###-####. Phone #: ###-#### Inspection requested via web by Toby Groves
Rear elevator lobby grid and west service corridor grid rough in ok cover.
West side of building sign whips shall terminate in a outdoor rated box
ELE16-00303 Electrical Rough-In7/28/20167/29/20167/29/2016 11:39:33 AMACANC
Inspect wall trim out on 2nd and 3rd floor. Inspect for remaining items needed for a TCO for this TI space. Contact is Toby Groves ###-####. Phone #: ###-#### Inspection requested via web by Toby Groves
Prewalk floors 2 and 3 ok for furniture. Thank you. Check corridor and stair lighting on both floors, remove flexible cord for temp power on 2, open boxes server rm, elec rm, 341, switch cover 342, west patio can trims, 3rd conference rm circiut inop, 368 furniture whip.
ELE16-02423 Temporary Service7/28/20167/29/20167/29/2016 9:11:18 AMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson
t/s u/g n ok
ELE16-02426 Final7/28/20167/29/20167/29/2016 9:10:45 AMACANC
Phone #: ###-#### Inspection requested via web by David Nelson
Needed temp service inspection
ELE16-02426 Temporary Service7/29/20167/29/20167/29/2016 9:10:35 AMPPASS
Phone #: ###-#### Inspection requested via web by David Nelson
t/s u/g n ok
ELE16-01134 Electrical Rough-In7/28/20167/29/20167/29/2016 12:00:00 AMAPASS
We are requesting a underground inspection in the alley way for tomorrow 7/29/16 late morning. Our contact on site is Bobby ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
east alley north 1/2 underground rough in ok cover. To verify with pictures areas not done. Scaffold will installed if issues with depth will address ofter scaffold gone.