Inspections for the day of: Tuesday, July 30, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01406 Electrical Rough-In7/30/20197/30/20197/30/2019 2:18:43 PMPPASS
Level 2 area A corridor and entry drops. Phone #: ###-#### Inspection requested via web by Tom Betty
Area noted adding N.W. exterior columns rough in ok cover
MIS19-00225 ELE-Conference7/30/20197/30/20197/30/2019 1:25:20 PMPFAIL
ELE and MEC- Newer AC unit on Northwest corner, no permit found for ELE or MEC.
Misc electrical issue left when last tenant vacated.
All Items found in other areas not in scope of work covered by BLD18-03533.
BCC 4-05-32- Code violations not to be retained.
Unable to locate mechanical permit for newer AC unit located on northwest corner.
110.3- Double duplex receptacle located in conference room not working. Found wire damaged by others, left damaged in ceiling.
110.12(B)- Repair all open and unsecured conduits.
210.63- A 15 or 20 amp 120 volt receptacle outlet shall be installed with in 25' of newer AC unit.
314.23- Boxes shall be secured to structure. Receptacles and MC hanging laying on top of file cabinet.
408.4- Panel directory for panel 2 shall be complete.
440.14- A disconnecting means shall be provided for newer AC unit located on N.W. corner.
ELE19-01406 Conference7/30/20197/30/20197/30/2019 1:13:58 PMPCANC
Electrical and Mechanical.
Newer AC unit installed on north west corner of building, no permit found for ELE or MEC.
Misc electrical issues after previous tenant vacated.
Wrong permit scheduled
ELE19-01088 Conference7/30/20197/30/20197/30/2019 12:02:13 PMPPASS
Discussed complete scope of work for office areas. Westerm and most eastern areas have circuitry added for office work stations. As of 12pn 7/30/19 Jimmy with Mountain power has been repairing items listed.
ELE19-01035 Rough-In Permanent Service7/29/20197/30/20197/30/2019 10:59:45 AMAPASS
Phone #: ###-#### Inspection requested via web by kevin blackmon
Called and had ELE attached to BLD19-00489. Rough in ok cover p/s u/g n ok
ELE19-02820 Temporary Service7/29/20197/30/20197/30/2019 9:59:34 AMAPASS
Phone #: ###-#### Inspection requested via web by William Andrews t/s u/g n ok
ELE19-02818 Temporary Service7/29/20197/30/20197/30/2019 9:59:09 AMAPASS
Phone #: ###-#### Inspection requested via web by William Andrews t/s u/g n ok
ELE19-02817 Temporary Service7/29/20197/30/20197/30/2019 9:58:43 AMAPASS
Phone #: ###-#### Inspection requested via web by William Andrews
t/s u/g n ok
ELE19-02694 Rough-In Permanent Service7/29/20197/30/20197/30/2019 9:41:32 AMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson
Rough in ok cover p/s u/g n ok
ELE19-02752 Rough-In Permanent Service7/29/20197/30/20197/30/2019 9:24:44 AMAPASS
Phone #: ###-#### Inspection requested via web by David Nelson
Rough in ok cover p/s u/g n ok