ELE15-00102
| ELE-Aging Inspection | 8/12/2019 | 8/12/2019 | 8/15/2019 2:47:24 PM | | FAIL |
|
|
Waiting on contractor
|
ELE19-02438
| Rough-In Permanent Service | 8/12/2019 | 8/12/2019 | 8/12/2019 3:19:47 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Hidajet Zahic A inspection is required for underground to well. Provide documentation on underground wire used. Appears to be standard 8-3 NM cable. Tried to call contact, unable to connect. Underground to service not in at time of inspection. House rough in ok cover p/s u/g n ok
|
ELE19-02808
| Conference | 8/9/2019 | 8/12/2019 | 8/12/2019 2:55:30 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mike McCarrel Discussed equipment grounding requirements on load side of transformer to 120/208 sub panel boards. As per 250.30(A)(1 thru 8) no connection is allowed to the grounded conductor and non-current carrying metal parts on load side of transformer in this case a system bonding jumper shall be installed at transformer. Equipment grounds shall be added to sub-feeds for panel boards due to non-metallic raceways present underground. Also discussed 210.8(B) GFCI requirements for other than dwelling kitchens. If a receptacles are installed for equipment in kitchen area they shall have GFCI protection, if chenged to hard wired appliances additional disconnecting means is required as per 422.31(A) and (B).
|
ELE18-01935
| Final | 8/9/2019 | 8/12/2019 | 8/12/2019 1:31:21 PM | A | PART |
|
|
Final for Units 201 ; 202 only Contact John (Homey) McElroy Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek In future check lockouts for hood and micro, and circuit directory for 201,202. Sign off in office when done. Egress not complete. Units noted only TCO ok
|
ELE19-02438
| Rough-In Permanent Service | 8/11/2019 | 8/12/2019 | 8/12/2019 9:42:32 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Hidajet Zahic 330.30- Mini split MC cables shall be supported so that no point exceeds 6'. North wall mostly. 1 hanging below trusses. 334.30- NM cables shall be secured with in 12" of boxes and supports not to exceed 4 1/2'. AC has no support, entry switch above box, bed switch above box, disposal wiring taken apart.
|
ELE19-02874
| Electrical Rough-In | 8/10/2019 | 8/12/2019 | 8/12/2019 8:49:57 AM | A | NR |
|
|
The crew will be ready to install inverter/panels by 11 AM. Call journeyman, Preston Seay, with any questions/timeframe. ###-#### Phone #: ###-#### Inspection requested via web by Rob Maes No one on site. Recall when present
|
ELE19-02892
| Rough-In Permanent Service | 8/9/2019 | 8/12/2019 | 8/12/2019 8:28:15 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s u/g n ok
|