Inspections for the day of: Wednesday, August 14, 2019.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02658 Final8/14/20198/14/20198/14/2019 3:55:38 PMPPASS
Contractor installed all floor covers. Final ok
ELE19-02658 Final8/9/20198/14/20198/14/2019 3:06:44 PMPFAIL
Anytime after store opening at 10:00 AM. Any questions contact Caleb Gaylord ###-#### Phone #: ###-#### Inspection requested via web by Caleb Gaylord
314.25- All boxes shall have covers. 3 existing floor boxes open, 2 with twist lock devices and 1 no device.
ELE19-02150 Final8/14/20198/14/20198/14/2019 2:29:56 PMPFAIL
Building is open Phone #: ###-#### Inspection requested via web by Kevin Oderkirk 110.3- 2 receptacles not working in imaging room.
210.8(B)- In other than dwelling units 120 volt, 15 and 20 amp receptacles located with in 6' of a sink shall have GFCI protection. Refer receptacle and exam rm receptacles.
406.12(5)- Tamper resistant receptacles shall be installed in business offices, corridors, waiting rooms and similar areas.
ELE19-01406 Rough-In Permanent Service8/14/20198/14/20198/14/2019 1:55:24 PMPPASS
Permanent Service Inspection and Cover inspection for exterior soffits, SE stairwell, and 2nd floor fur outs.
Contact John Mittleider.
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Areas noted with fur outs in B204, B206, B215, B218 rough in ok cover 55k available fault current
p/s u/g n ok
ELE19-02808 Electrical Rough-In8/13/20198/14/20198/14/2019 11:56:29 AMAPASS
Underslab raceways for cover Phone #: ###-#### Inspection requested via web by Mike McCarrel
Conduits noted rough in ok cover
ELE19-02715 Electrical Rough-In8/13/20198/14/20198/14/2019 11:38:04 AMAPASS
Bill Peace is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Phase 1 as noted on contractor print wall rough in ok cover
ELE19-02825 Electrical Rough-In8/13/20198/14/20198/14/2019 10:09:22 AMAPASS
Jose Phone #: ###-####
Complete floor grid rough in ok cover