ELE18-00715
| Final | 8/2/2018 | 8/2/2018 | 8/2/2018 2:23:00 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Todd Hall Final ok
|
ELE18-02922
| Electrical Rough-In | 8/1/2018 | 8/2/2018 | 8/2/2018 2:22:07 PM | P | PART |
|
|
inspection for underground from office building to gate, pole light and storage buildings. Please inspect early afternoon so trenches can be filled back before end of day. Also need consult on another item on site. please call Todd Phone #: ###-#### Inspection requested via web by Todd Hall Called as requested, no answer, left message. Underground for entry area, gate, light pole, and to buildings P, and B only. Rough in ok cover
|
ELE18-02064
| Electrical Rough-In | 8/1/2018 | 8/2/2018 | 8/2/2018 1:24:13 PM | P | NR |
|
|
Please call prior for access. Call Jarod at Mountain Power ###-#### for access key code. Phone #: ###-#### Inspection requested via web by Kevin Perez Misc wiring to complete and misc make up Recall when complete.
|
ELE18-02920
| Temporary Service | 8/1/2018 | 8/2/2018 | 8/2/2018 11:15:03 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Heath Thomas t/s u/g n ok
|
ELE18-01440
| Final | 8/1/2018 | 8/2/2018 | 8/2/2018 10:36:42 AM | A | PASS |
|
|
Contact is Jim Noll. Please call at ###-#### 30 minutes prior to arriving. GC personnel will be on site. Phone #: ###-#### Inspection requested via web by Scott Campbell Final ok
|
ELE18-02286
| Final | 8/1/2018 | 8/2/2018 | 8/2/2018 10:03:00 AM | A | FAIL |
|
|
Just call before you get there and I''ll meet you so I can remove the panel cover for you. Phone #: ###-#### Inspection requested via web by Dan Hilke 250.92- Metal nipple entering thru concentric KO from meter shall have a bonding bushing bonding complete. Bonding bushing installed, no lug on bonding bushing. 250.94- Bonding strap installed on service lateral riser, informed a llisted intersystem bond bar shall be installed. 2 ground rods installed on fence line, rest of corrections ok.
|
ELE18-02286
| Permanent Service | 8/2/2018 | 8/2/2018 | 8/2/2018 10:02:21 AM | P | PASS |
|
|
Just call before you get there and I''ll meet you so I can remove the panel cover for you. Phone #: ###-#### Inspection requested via web by Dan Hilke p/s u/g rec ok
|
ELE18-02230
| Final | 8/1/2018 | 8/2/2018 | 8/2/2018 9:13:59 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jesse Fuentes Final ok
|
ELE18-02300
| Electrical Rough-In | 8/1/2018 | 8/2/2018 | 8/2/2018 8:29:32 AM | A | PASS |
|
|
Underground branch circuit homeruns. As early as possible please Phone #: ###-#### Inspection requested via web by Jason Parke Underslab branch conduits rough in ok cover
|