Inspections for the day of: Monday, August 22, 2016.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-01348 Conference8/22/20168/22/20168/23/2016 11:12:19 AMPDONE
Inspect progress on panic hwd. in Garage EXP Discuss all Electrical Rooms in SWHQ , are we in compliance with 110.26 Personnel Doors? Phone #: ###-#### Inspection requested via web by Tom Betty
Discussed if panic hardware require on all floors where electrical rooms are located. NEC 110.26(C)(3)- States equipment rated 800 amps or more that contain overcurrent devices, switching devices, or control devices, doors for egress located within 25' shall have panic hardware. As per Daryl DeGrange each room with a disconnecting means under 800 amp panic hardware is not required, if disconnects are rated 800 amp or larger panic hard ware required.
ELE16-01628 Final8/19/20168/22/20168/22/2016 3:34:17 PMPNR
Request for Temp occupancy . Call Ryan - ###-#### Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Outdoor egress not complete in front due to auning not in place yet.
210.8- All GFCI receptacles located in ceiling around bar shall be located in a readily accessible location.
ELE15-00495 Rough-In Permanent Service8/22/20168/22/20168/22/2016 2:50:28 PMPCANC
5 Story 4th floor Ballroom Ceiling for cover inspection.
Contact is Mark Gibson ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves
Needed rough in only.
ELE15-00495 Electrical Rough-In8/22/20168/22/20168/22/2016 2:50:01 PMPPASS
5 Story 4th floor Ballroom Ceiling for cover inspection.
Contact is Mark Gibson ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves
Ceiling inspection for this area for 2 3" conduits feeding roof top units. Rough in ok cover
ELE16-01652 Electrical Rough-In8/21/20168/22/20168/22/2016 2:48:13 PMPPASS
Underground north area of center core Phone #: ###-#### Inspection requested via web by John Rourke
Discussed bonding around fountain area. Shall bond shell, 4 stubs for equipotential plane, metal spray housings. GFCI protection of LED lights depend on transformer type. North underground 20' to south rough in ok cover
ELE16-01421 Final8/22/20168/22/20168/22/2016 1:16:41 PMPPASS
Please call me half an hour before inspection for access. Thank you Shaun ###-#### Phone #: ###-#### Inspection requested via web by Shaun Kirkman Final ok
ELE16-02726 Electrical Rough-In8/22/20168/22/20168/22/2016 12:28:41 PMPCANC
Please call prior to inspection. ###-#### Phone #: ###-#### >> Inspection requested via web by BARRY KENDALL Inspection cancelled from web by: BARRY KENDALL
ELE16-02702 Final8/18/20168/22/20168/22/2016 12:24:21 PMACANC
Phone #: ###-#### Inspection requested via web by alfredo arteaga
Needed permanent service inspection
ELE16-02702 Permanent Service8/22/20168/22/20168/22/2016 12:23:34 PMPFAIL
Phone #: ###-#### Inspection requested via web by alfredo arteaga
110.14- Aluminum conductors shal be coated with a oxide inhibitor when terminated.
250.53(A)(1)- Where rod is used as grounding electrode system it shall be supplemented by an additional rod.
ELE16-02681 Electrical Rough-In8/22/20168/22/20168/22/2016 10:21:42 AMAPASS
Phone #: 8694676 >> Inspection requested via mobile web by Barry Spencer
Listing confirmed rough in ok
ELE16-02613 Final8/19/20168/22/20168/22/2016 9:52:23 AMANH
Inspection requested via web by Randy Fletcher
No answer at door no contact number provided.
ELE16-01991 Final8/21/20168/22/20168/22/2016 9:33:49 AMAFAIL
key on top of patio light Phone #: ###-#### Inspection requested via web by Therrin Robertson
230.70- Disconnect for detached garage shall disconnect power in the off position.
440.11- Furnace shall have a disconnecting means
ELE16-01990 Final8/21/20168/22/20168/22/2016 9:30:14 AMAFAIL
key on top of patio light Phone #: ###-#### Inspection requested via web by Therrin Robertson
230.70- Disconnect for detached garage shall disconnect power in the off position.
440.11- Furnace shall have a disconnecting means.
ELE16-02706 Conference8/22/20168/22/20168/22/2016 8:59:18 AMADONE
Phone #: ###-#### Inspection requested via web by Ben Archibald
Discussed the existing panel location in an existing bathroom.
BCC 4-05-31(A)- Panel shall not be located in a bathroom.
310.15- Service feeders shall be sized properly for 200 amp panel from original install.
Contractor to correct address should be 2100 . Broadway Ave.