Inspections for the day of: Thursday, August 22, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03131 Electrical Rough-In8/22/20198/22/20198/22/2019 3:57:57 PMPFAIL
Driveway heat before cover. Please call Steve with any questions. Thank you Phone #: ###-#### Inspection requested via web by Steve Blackmer
426.22(B)- All but 1" to 6" of non-heating lead shall be enclosed in raceway.
426.22(C)- Bushings shall be provided where cold leads enter conduit.
* Provide manufacturers instructions.
ELE19-03117 Electrical Rough-In8/22/20198/22/20198/22/2019 3:01:41 PMPPASS
Underground and exterior walls only. Phone #: ###-#### Inspection requested via web by Dave Brueggemann
Perimeter wall and bar under slab rough in ok cover
ELE19-03158 Electrical Rough-In8/22/20198/22/20198/22/2019 2:07:25 PMPPASS
Phone #: ###-#### Inspection requested via web by Brad Girard
BLD permit under review for plan mod for basement window wells.
Main level only rough in ok cover
ELE19-03135 Temporary Service8/22/20198/22/20198/22/2019 1:33:24 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE19-02974 Final8/21/20198/22/20198/22/2019 11:25:40 AMAPASS
Blue Raven Electrician - Shaun Shafer: ###-####
Install Crew Lead: Jay Walters: ###-####
Install Manager - Brian Prussia (call with questions regarding project): ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting
Final ok
ELE19-02770 Rough-In Permanent Service8/21/20198/22/20198/22/2019 11:16:36 AMAFAIL
Inspection requested via web by Bob Glenn
300.4- Nail plate needed in guest bath 12-2 for receptacle, marked with X.
300.15- NM cable shall terminate in a box. Photo cell above meterbase not stuffed.
* Hood wire hanging in bedroom ceiling.
2, 10-2 hanging from patio ceiling?
ELE19-02391 Electrical Rough-In8/22/20198/22/20198/22/2019 10:43:48 AMPCANC
elevator lobby 8th floor Phone #: ###-#### >> Inspection requested via web by Mark M Inspection cancelled from web by: Mark M
ELE19-01813 Final8/22/20198/22/20198/22/2019 10:18:17 AMANH
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn
No access due to finishing hard wood floor. Must reschedule.
ELE19-02147 Final8/21/20198/22/20198/22/2019 9:59:51 AMAPASS
Garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk
Final ok