ELE19-03134
| Final | 8/23/2019 | 8/26/2019 | 8/26/2019 2:31:57 PM | P | PASS |
|
|
Call Fred with questions please ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Labels complete. Final ok
|
ELE19-03134
| Permanent Service | 8/20/2019 | 8/26/2019 | 8/26/2019 2:29:27 PM | P | PASS |
|
|
Please call Fred with any questions ###-####. Thanks! Phone #: ###-#### Inspection requested via web by Clayton Morgan No other work performed just raised over head mast. p/s o/h rec ok
|
ELE19-00374
| Final | 8/23/2019 | 8/26/2019 | 8/26/2019 1:49:14 PM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI 250.94(A)(1)- Inter system bond shall be accessible for use.Buried in trim work. 410.16- Luminaires located in closet shall be installed at least 12" from storage shelf. BCC 4-05-24(D)- Electrical inspector shall have access to all areas work has been done. Detached garage and mechanical closet on exterior.
|
ELE18-04603
| Final | 8/23/2019 | 8/26/2019 | 8/26/2019 1:44:22 PM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI 356.30(1)- LFNC when installed in lengths greater than 6' shall have supports not to exceed 3' in length. AC 440.6- Overcurrent protection for AC unit shall not exceed value on name plate. 25 amp max 30 amp installed.
|
ELE19-03082
| Final | 8/24/2019 | 8/26/2019 | 8/26/2019 12:23:49 PM | A | PASS |
|
|
Corrections have been made since last inspection. Phone #: ###-#### Inspection requested via web by Dan Hilke Final ok
|
ELE18-01935
| Electrical Rough-In | 8/23/2019 | 8/26/2019 | 8/26/2019 9:48:51 AM | A | PASS |
|
|
John Phone #: ###-#### All levels server room drop lids, Level 3 public bathroom droplid, must have larger access, Level 4 406 floor heat rough in ok cover
|
ELE19-03174
| Electrical Rough-In | 8/23/2019 | 8/26/2019 | 8/26/2019 9:25:51 AM | A | PART |
|
|
Please call Mike H. Phone #: ###-#### Inspection requested via web by Kevin Perez Discussed if equipment grounding conductors were required to switch bank where box fill tight. Electrical engineer has drawn in equipment grounding conductors on print so will be required to be installed. kitchen walls and salad wall as noted on contractor print rough in ok cover
|