Inspections for the day of: Thursday, September 11, 2014.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01607 ELE-Aging Inspection9/11/20149/11/20149/11/2014 3:38:41 PM DONE
Still under construction
ELE14-01962 Final9/11/20149/11/20149/11/2014 3:33:58 PMPFAIL
Phone #: ###-#### Inspection requested via web by Celinda Winters
210.8(B)(5) Sinks — where receptacles are installed within 1.8 m
(6 ft) of the outside edge of the sink they shall have GFCI protection
517.18 (B)- General Care Areas All
receptacles shall be listed “hospital grade” and shall be so
identified.
ELE14-02529 Electrical Rough-In9/11/20149/11/20149/11/2014 3:15:28 PMPPASS
Bob Phone #: ###-#### Wall rough in ok cover
ELE14-01960 Final9/11/20149/11/20149/11/2014 2:24:03 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
ELE14-02213 Electrical Rough-In9/10/20149/11/20149/11/2014 1:48:27 PMPPART
Mike Phone #: ###-#### East lot, south west lot, in building, communication conduits, west to nurses station, S. E. corner underground rough in ok cover
ELE14-02492 Electrical Rough-In9/11/20149/11/20149/11/2014 1:09:40 PMPPASS
Chris is contact. Thank you Phone #: ###-#### Inspection requested via web by Chris Chesnut Different contracor doing family room ele14-02416 Kitchen remodel rough in ok cover
ELE14-01106 Final9/11/20149/11/20149/11/2014 12:31:26 PMPPASS
Joe Phone #: ###-#### Final ok
ELE14-02490 Final9/10/20149/11/20149/11/2014 10:43:15 AMAPASS
If you have any questions, please call the office. Thank you. Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
ELE14-02528 Electrical Rough-In9/10/20149/11/20149/11/2014 10:27:08 AMAPASS
Install 30 amp 2 pole/wire new heat pump
Trailer Space #9 Phone #: ###-#### Inspection requested via web by Stuart Welton Rough in ok
ELE14-02528 Final9/11/20149/11/20149/11/2014 10:02:33 AMPPASS
Install 30 amp 2 pole/wire new heat pump
Trailer Space #9 Phone #: ###-#### Inspection requested via web by Stuart Welton Final ok
GCE14-00144 GCE-Final9/10/20149/11/20149/11/2014 9:29:30 AMAPASS
###-#### (Mandatory Inspection) UL listing confirmed coolers final ok
GCE14-00123 GCE-Rough-In9/10/20149/11/20149/11/2014 9:28:20 AMAPASS
Kyle ###-#### Ceiling grid rough in ok cover
ELE14-00744 Final9/10/20149/11/20149/11/2014 8:44:48 AMAPASS
Darrell Phone #: ###-#### Final ok