Inspections for the day of: Friday, September 13, 2019.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03469 Electrical Rough-In9/13/20199/13/20199/13/2019 2:22:52 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Walls rough in ok cover
ELE19-03295 Electrical Rough-In9/13/20199/13/20199/13/2019 1:28:20 PMPPASS
wall cover Phone #: ###-#### Inspection requested via web by David Feller
Accesses required for center of front soffit and at left show window receptacle will confirm on final. Walls and front soffit rough in ok cover.
ELE19-01668 Final9/13/20199/13/20199/13/2019 12:48:15 PMPPASS
Replace monument sign. All work had to be done on weekend. All Primary power to remain as is. Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok
ELE19-01668 Electrical Rough-In9/13/20199/13/20199/13/2019 12:47:46 PMPPASS
Replace 1 monument sign. Work had to be completed on weekend. All Primary power to remain as is. Phone #: ###-#### Inspection requested via web by Ken Olsen
Listing and disconnecting means confirmed. Rough in ok
ELE19-03270 Electrical Rough-In9/12/20199/13/20199/13/2019 11:49:57 AMAPASS
Underground Inspection
Contact Alex Ybarra
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
Under ground rough in ok cover
ELE18-01935 Final9/12/20199/13/20199/13/2019 11:17:46 AMAPART
Final inspections for 2nd floor hall, 2nd floor trash room, 2nd floor com room, 3rd floor hall, 3rd floor trash room, 3rd floor bath room, 3rd floor com room.
Contact electrician on-site - John (Homey) McElroy
Thank you.
Phone #: ###-#### Inspection requested via web by Cathy Duchek *406 will need TCO prior to appliances being set. All electrical to be safed off and appliances to be set prior to actual final date.
*506 to be removed from this permit and to be permitted seperately.
Level 3 bathroom heater cover not in place.
Rest of list signed off in office. TCO ok
ELE19-02529 Electrical Rough-In9/12/20199/13/20199/13/2019 10:16:18 AMAPASS
Requesting 10:00 am inspection time. Remove two Jacksons wall signs replace with new Extra Mile signs. All Primary power to remain as is. Phone #: ###-#### Inspection requested via web by Ken Olsen
Listing confirmed on sign and power supply. Rough in ok
ELE19-03015 Electrical Rough-In9/12/20199/13/20199/13/2019 9:45:24 AMAPASS
John Phone #: ###-####
Wall rough in ok cover
ELE19-03424 Rough-In Permanent Service9/12/20199/13/20199/13/2019 9:16:38 AMAFAIL
Phone #: ###-#### Inspection requested via web by Tyler Ridley
Idaho power requires 16' minimum over residential driveway. Approx. 13 ' at time of inspection. Increase to 16 and recall.