ELE19-03467
| Permanent Service | 9/16/2019 | 9/17/2019 | 9/17/2019 3:12:00 PM | P | PASS |
|
|
Upgrading service, installing an all-in-one meterbox ; breaker panel. Not sure exactly what time we''ll be ready for inspection, but if you want to text/call ahead I can give you a better idea of where we''re at and if we''re ready. Phone #: ###-#### Inspection requested via web by Dan Hilke p/s o/h rec ok
|
ELE19-02424
| Final | 9/16/2019 | 9/17/2019 | 9/17/2019 2:48:41 PM | P | FAIL |
|
|
Please call Lynn prior to arrival. Phone #: ###-#### Inspection requested via web by Lynn Proctor 210.71- Meeting rooms at least 215 sq.ft shall have a receptacle located in the floor. This floor receptacle shall be installed in a listed floor box as per 314.27(B). All other areas checked out OK. OK to move in furniture.
|
ELE18-02706
| Final | 9/17/2019 | 9/17/2019 | 9/17/2019 2:09:03 PM | P | PASS |
|
|
Final ok
|
ELE19-03489
| Permanent Service | 9/16/2019 | 9/17/2019 | 9/17/2019 12:20:21 PM | A | PASS |
|
|
This inspection is for reconnection of existing service. Phone #: ###-#### Inspection requested via web by Dan Surerus Discussed wiring in foam walls. Shall be 1 1/4" from framing surface for protected from physical damage. Cutting 2 1/2" deep notches in foam for channels. p/s o/h rec ok
|
ELE18-01935
| Final | 9/16/2019 | 9/17/2019 | 9/17/2019 11:39:58 AM | A | PASS |
|
|
Final inspections for - Unit 309, and 204 5th floor hall, 5th floor trash room, 5th com room, 4th floor hall 4th floor trash room, 4th floor com. Room and south stairs // Contact John (Homey) McElroy Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas noted, added level 1 TI vanilla space TCO ok
|
ELE19-03472
| Final | 9/16/2019 | 9/17/2019 | 9/17/2019 10:41:47 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Tyler Ridley 110.3- Open ground shown on east garage wall receptacle. 250.24(A)(1)- Grounding electrode conductor shall be connected to the grounded conductor at the service disconnecting means. At time of inspection bonding of neutral done in panel on load side of service disconnecting means. Grounded conductor shall not be connected to non-current carrying metal parts on load side of service disconnecting means as per 250.24(A)(5). Called number provided and reached someone named Brandy, did not leave message, not sure if right party.
|
ELE19-02613
| Final | 9/16/2019 | 9/17/2019 | 9/17/2019 10:04:15 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher Sign final ok
|
ELE19-02555
| Final | 9/16/2019 | 9/17/2019 | 9/17/2019 8:44:11 AM | A | FAIL |
|
|
Code 9701 - will get you into the lock box to unlock the door. Phone #: ###-#### Inspection requested via web by Winters LLC 408.4- Circuit directory shall be complete. relabel. 422.31- Confirm water heater disconnecting means. WH located on top of bath above ceiling. Please have complex management cover open junction box on small post in front of this address.
|