Inspections for the day of: Wednesday, September 18, 2019.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03140 Final9/18/20199/18/20199/18/2019 4:19:38 PMPPASS
Duane Oreilly contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Correction made. Final ok
ELE19-02771 Final9/18/20199/18/20199/18/2019 2:44:38 PMPFAIL
Contact: Mike Mulvahill Phone #: ###-#### Inspection requested via web by Deb Gooden
210.8(B)- GFCI protection shall be supplied for drinking fountain. Contact stated ordering as we speak.
No print on site to reference, south door of warehouse does not have exit or out emergency egress. Contact stated items are not shown on print.
ELE19-02772 Final9/18/20199/18/20199/18/2019 2:41:43 PMPPASS
Contact: Mike Mulvahill Phone #: ###-#### Inspection requested via web by Deb Gooden
Final ok
ELE19-01440 Final9/18/20199/18/20199/18/2019 1:52:27 PMPFAIL
Phone #: ###-#### Inspection requested via web by Jason Wicks
352.46- Where a conduit enters a box, fitting, or enclosure a bushing of adapter shall be provided to protect the wiring from physical damage.
ELE18-01935 Final9/17/20199/18/20199/18/2019 11:25:29 AMAPART
Final Inspection for Units 203, 513, 514, and 515.
Contact John (Homey) McElroy
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Units noted signed off in office. TCO ok
ELE19-03488 Conference9/17/20199/18/20199/18/2019 9:57:08 AMADONE
Please call Luke to discuss top out of plywood and sheetrock in hallways and general installation nature. Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo
Discussed the cover of 1 side of walls, (top out) only. BCC 4-05-23 It shall be unlawful to conceal any wiring or equipment prior to having same inspected by City of Boise Electrical inspector. Contact stated no wiring in areas in question so top out OK
ELE19-03488 Electrical Rough-In9/18/20199/18/20199/18/2019 9:52:19 AMPPART
Please call Luke to discuss top out of plywood and sheetrock in hallways and general installation nature. Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo
One side cover on upper portion of walls only rough in ok cover
ELE19-02169 Electrical Rough-In9/16/20199/18/20199/18/2019 9:33:24 AMAPASS
Contact: Cindy Wolff, final ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden
Grid complete. Grid rough in ok cover