Inspections for the day of: Friday, September 20, 2019.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02445 Electrical Rough-In9/20/20199/20/20199/20/2019 2:31:51 PMPPASS
Rough-in for utility area. Later in day if possible Phone #: ###-#### Inspection requested via web by Michael Kennedy
Laundry area rough in ok cover
ELE19-03172 Final9/17/20199/20/20199/20/2019 1:45:59 PMPNH
Please call Brodie with any questions @ ###-####. Phone #: ###-#### Inspection requested via web by William Salts
Unable to locate some one on site with ladder for access to roof where condensing units are located. Recall when accessible.
ELE19-03130 Electrical Rough-In9/20/20199/20/20199/20/2019 1:17:05 PMPPASS
There will be someone there. If you have any questions please feel free to contact Luke ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Missing exhaust fan in bath. Walls only rough in ok cover
ELE19-00898 Electrical Rough-In9/19/20199/20/20199/20/2019 11:32:16 AMAPASS
Key for access will be right down the hall at J E Suttons office. Just need approval for ceiling grid cover. Phone #: ###-#### Inspection requested via web by Trevor Soesbe
Corrections complete, Thank you. Grid rough in ok cover.
ELE18-01935 Final9/19/20199/20/20199/20/2019 11:03:09 AMAPART
Final inspection for Units 406, 507, 509, 511, 512, north stairs/roof/pent house/3rd floor patio/2nd floor court yard
Contact John (Homey) McElroy
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Items remaining-
1- 110.3- Level 2 court yard planter ground boxes shall have wire connectors listed for wet locations.
2- 210.8(B)- Level 3 patio disposal receptacle located outdoors shall have GFCI protection. 2 pole 50 amp receptacle in garage shall have GFCI protection.
3- 314.15- All exterior boxes shall be sealed to prevent moisture from entering box or wall.
4- 590.6(B)- All temp power shall have GFCI protection. All 250 receptacles need it.

This TCO is for construction personel still only allowed access. Signed off podium and phase 2 permits for TCO ok
3-
ELE19-03541 Electrical Rough-In9/20/20199/20/20199/20/2019 9:01:31 AMAPASS

R/I inspection of main entrance, 20A and 50A outlets, remodel style can lights (reason only whips are in hard lid).
Contact Luke Hardy
Thank you
Phone #: ###-#### Inspection requested via web by Cathy Duchek
Main South East entrance walls and lids rough in ok cover