Inspections for the day of: Thursday, September 26, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-00895 Final9/25/20199/26/20199/26/2019 2:51:12 PMPPART
Electrical final, Brett is the contact. Phone #: ###-#### Inspection requested via web by Deb Ipsen
210.8(B)- All 120 volt receptacles located in kitchen area shall have GFCI protection. Left of serving window and right of ovens on 1/2 wall.
440.6- Fuse for small roof top unit min fuse over 30 amp, 30 amp fuses installed in disconnect.
Contractor to correct by the time we do an AM fly by.
Ovens from existing kitchen to be brought over at future time. Will need to verify these connections.
TCO OK
ELE19-03226 Electrical Rough-In9/26/20199/26/20199/26/2019 2:49:14 PMPPASS
Call with any questions. We''re on site Phone #: ###-#### Inspection requested via web by Kory Peterson
Entry and entry dividing wall not ready.
Bathrooms, kitchen, back corridor walls and hardlids rough in ok cover
ELE19-00789 Final9/25/20199/26/20199/26/2019 1:37:41 PMPPASS
electrical final for service on module classroom. Service was overhead and is now underground. Phone #: ###-#### Inspection requested via web by Deb Ipsen Final ok
ELE19-02900 Final9/25/20199/26/20199/26/2019 12:09:45 PMAPART
Phone #: ###-#### Inspection requested via web by Debby Pierce
Phase 1 TCO ok
ELE19-03636 Electrical Rough-In9/25/20199/26/20199/26/2019 11:27:54 AMAPASS
Underground and bonding for swimming pool Phone #: ###-#### Inspection requested via web by Lars Johnson
Underground and bonding from equipment to shell, 4 corners, and bond rough in ok cover.
ELE19-02712 Final9/26/20199/26/20199/26/2019 11:10:28 AMPFAIL
590.6(B)- All temp power other than 120 volt shall have GFCI protection. 250 did not trip when spot checked.
ELE19-03589 Rough-In Permanent Service9/26/20199/26/20199/26/2019 10:47:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn

Underground not complete, expansion joint not in place. Rough in ok cover p/s u/g n ok
ELE19-03635 Temporary Service9/26/20199/26/20199/26/2019 10:46:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
t/s u/g n ok
ELE19-03342 Rough-In Permanent Service9/26/20199/26/20199/26/2019 10:24:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Underground to service in a different location. Attic boxes trimmed on rough in around furnace. Rough in ok cover p/s u/g n ok
ELE19-03488 Electrical Rough-In9/25/20199/26/20199/26/2019 9:52:03 AMAPASS
Wall R/I cover inspection west of elevators. Please call Luke for any questions. Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo
All walls east of elevator rough in ok cover
ELE19-03270 Final9/26/20199/26/20199/26/2019 9:08:39 AMAFAIL
Final inspection for mini cell site.
Contact Alex Ybarra
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek
250.24- A grounding electrode conductor shall be connected to the grounded conductor at the service main discnnecting means. Grounds and neutrals seperated at time of inspection.