ELE19-02945
| Electrical Rough-In | 9/6/2019 | 9/6/2019 | 9/6/2019 3:48:44 PM | P | PASS |
|
|
Ceiling Cover Phone #: ###-#### Inspection requested via web by David Feller Grid rough in ok cover
|
ELE19-03349
| Permanent Service | 9/6/2019 | 9/6/2019 | 9/6/2019 2:38:06 PM | P | PASS |
|
|
MITCH- PLEASE CALL 30 MIN PRIOR Phone #: ###-#### Service to be energized on a temporary basis. New meter base and mast at this time, will be correcting issues with too many current carrying conductors in surface conduits ect. p/s o/h rec ok
|
ELE19-02312
| Final | 9/6/2019 | 9/6/2019 | 9/6/2019 2:35:38 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Tyler Bowen Final ok
|
ELE19-02841
| Final | 9/6/2019 | 9/6/2019 | 9/6/2019 1:52:00 PM | P | FAIL |
|
|
Final inspection please. Thank you! Phone #: ###-#### Inspection requested via web by Kyle Lott 300.15- All cables shall terminate in a box. Upstairs MC up thru floor with 5' of loose wire and open stripped ends exposed. 314.25- All boxes shall have covers. Open junction box in ceiling against wall. Open switch box 330.30- MC shall be secured with in 12" of a box. Couple locations.
|
ELE17-03140
| Final | 9/5/2019 | 9/6/2019 | 9/6/2019 1:10:48 PM | A | FAIL |
|
|
Duane Oreilly is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce 314.25- All boxes shall have covers. 330.30- MN cable shall be secured with in 12" of a box. Building permit noted some areas of grid being replaced. History of inspections show no grid inspection performed. Just in from front door looked up and noticed 2 open boxes and KO seals needed and unsecured MC cable. Will need to meet contact on site with ladder to check areas above grid.
|
ELE19-03212
| Permanent Service | 9/6/2019 | 9/6/2019 | 9/6/2019 11:40:55 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Contractor failed to include permenant service in inspection request. Inspector 345 inspected and stickered meter base on 9-3-19. Confirmed sticker posted.
|
ELE19-02011
| Final | 9/5/2019 | 9/6/2019 | 9/6/2019 11:29:23 AM | A | PASS |
|
|
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE19-02994
| Permanent Service | 9/5/2019 | 9/6/2019 | 9/6/2019 10:44:46 AM | A | FAIL |
|
|
this is a service inspection. Padlock #2914. Any questions feel free to call Jason at ###-#### Phone #: ###-#### Inspection requested via web by Sherry Allen 250.24- AC system shall have a grounding electrode conductor connected to the grounded conductor. Unable to verify grounding electrode and main bonding jumper missing to bond grounded conductor.
|
ELE18-01935
| Final | 9/5/2019 | 9/6/2019 | 9/6/2019 10:16:43 AM | A | PART |
|
|
Final inspection for units 206, 207, and 209 Contact electrician on-site John McElroy (Homey) Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Units noted signed off in office. TCO ok
|
ELE19-03174
| Electrical Rough-In | 9/5/2019 | 9/6/2019 | 9/6/2019 9:32:38 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jeremy Cloud Back kitchen wall changing. Walls and soffits and bathrooms as noted on contractor print rough in ok cover.
|
ELE19-02825
| Final | 9/5/2019 | 9/6/2019 | 9/6/2019 9:07:08 AM | A | PASS |
|
|
jose Phone #: ###-#### Final ok
|
ELE18-03625
| Final | 9/5/2019 | 9/6/2019 | 9/6/2019 7:24:50 AM | A | CANC |
|
|
Please give me half an hour notice before inspection to insure access. Thank you Shaun ###-#### Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman Inspection cancelled from web by: Shaun Kirkman
|