Inspections for the day of: Tuesday, October 9, 2018.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03873 Conference10/9/201810/9/201810/9/2018 1:31:01 PMPPASS
Please call Jose.

Go over Fire Pump. Phone #: ###-#### Inspection requested via web by Kevin Perez Discussed disc means on exterior of building. NFPA 20 does not allow disc between Power source and pump control panel unless supplied by multiple sources. If disc is installed, the power source becomes unreliable, and back up power is required.
ELE18-01391 Electrical Rough-In10/5/201810/9/201810/9/2018 1:22:01 PMPPASS
Contact Scott for level 5 roof parapet wall rough in. Phone #: ###-#### Inspection requested via web by Tom Betty Rough in walls only ok to cover
ELE18-02756 Final10/8/201810/9/201810/9/2018 11:44:15 AMAPASS
garage code 2724 Phone #: ###-#### Inspection requested via web by Darryn Coburn Corrections made final ok
ELE18-02624 Final10/9/201810/9/201810/9/2018 10:37:26 AMAPASS
GARAGE CODE 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE18-02802 Final10/4/201810/9/201810/9/2018 10:36:50 AMAPASS
Phone #: ###-#### Inspection requested via web by Steve VanWinkle Sign only final ok