ELE18-03873
| Conference | 10/9/2018 | 10/9/2018 | 10/9/2018 1:31:01 PM | P | PASS |
|
|
Please call Jose.
Go over Fire Pump. Phone #: ###-#### Inspection requested via web by Kevin Perez Discussed disc means on exterior of building. NFPA 20 does not allow disc between Power source and pump control panel unless supplied by multiple sources. If disc is installed, the power source becomes unreliable, and back up power is required.
|
ELE18-01391
| Electrical Rough-In | 10/5/2018 | 10/9/2018 | 10/9/2018 1:22:01 PM | P | PASS |
|
|
Contact Scott for level 5 roof parapet wall rough in. Phone #: ###-#### Inspection requested via web by Tom Betty Rough in walls only ok to cover
|
ELE18-02756
| Final | 10/8/2018 | 10/9/2018 | 10/9/2018 11:44:15 AM | A | PASS |
|
|
garage code 2724 Phone #: ###-#### Inspection requested via web by Darryn Coburn Corrections made final ok
|
ELE18-02624
| Final | 10/9/2018 | 10/9/2018 | 10/9/2018 10:37:26 AM | A | PASS |
|
|
GARAGE CODE 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE18-02802
| Final | 10/4/2018 | 10/9/2018 | 10/9/2018 10:36:50 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Steve VanWinkle Sign only final ok
|