Inspections for the day of: Friday, November 15, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03911 Electrical Rough-In11/14/201911/15/201911/15/2019 2:31:57 PMPPASS
Phone #: ###-#### Inspection requested via web by Jonathan Poot Back area Sub panel,Refer, Dish/disp, misc. counter receps and small office area.
ELE19-03324 Electrical Rough-In11/15/201911/15/201911/15/2019 1:26:24 PMPPASS
ceiling inspection Corrections made Ceiling ok to cover
ELE19-00108 Electrical Rough-In11/15/201911/15/201911/15/2019 12:46:53 PMPPASS
Unit 303 Floor Heat
Contact Craig Timmons
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Floor heat only ok to cover
ELE19-04224 Final11/15/201911/15/201911/15/2019 11:55:35 AMPPASS
Jose Phone #: ###-#### Final ok
ELE19-04396 Final11/15/201911/15/201911/15/2019 11:50:47 AMAPASS
Final electrical inspection in conjunction with Old Dominion final solar inspection.

Thank you ; have a great day! Phone #: ###-#### final ok
ELE19-04400 Final11/14/201911/15/201911/15/2019 11:49:27 AMAPASS
homeowner will be home and is leaving the garage door open for access to the electric panel. Plans are at the inverter which is behind the gate which will be propped open for you. Phone #: ###-#### Inspection requested via web by Matt Oranday final ok
ELE19-01482 Final11/14/201911/15/201911/15/2019 10:42:58 AMAPART
Final electrical inspection needed for roof and exterior Please call Jared with any questions. Phone #: ###-#### Inspection requested via web by Angela Stears Partial only. Exterior light is up, Unit 104 Mini split has a 15A max ocpd. 20A installed. Partial final ok (Note: HVAC contractor had been trouble shooting problems in Mini spit rooftop units. Many cover for lowvolt connections were missing screws.)
ELE19-04368 Final11/13/201911/15/201911/15/2019 10:12:23 AMAPASS
Contact: Matt Cinko Phone #: ###-#### Inspection requested via web by Deb Gooden exterior Hose bib heater in Greyhound bus area. final ok
ELE19-03701 Final11/14/201911/15/201911/15/2019 9:50:35 AMAPASS
Request by Miguel with amp electric Phone #: ###-#### Inspection requested via web by Greg Traudt final ok
ELE19-04414 Rough-In Permanent Service11/14/201911/15/201911/15/2019 9:17:08 AMAPASS
Please contact me when done Phone #: ###-#### Inspection requested via web by Thomas wilson Underground ok p/s u/g n ok
ELE19-04400 Final11/14/201911/15/201911/14/2019 11:38:23 AMACANC
Homeowner will be there on site with garage open. Plans are at the inverter next to meter, behind the gate (which is open). United electric did electrical tie in and they will have a final today as well Phone #: ###-#### >> Inspection requested via web by Matt Oranday Inspection cancelled from web by: Matt Oranday