ELE18-02216
| Electrical Rough-In | 11/7/2018 | 11/7/2018 | 11/7/2018 3:11:22 PM | P | PASS |
|
|
Paul Phone #: ###-#### ceiling only ok to cover
|
ELE18-04297
| Rough-In Permanent Service | 11/6/2018 | 11/7/2018 | 11/7/2018 2:36:03 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Neal Rumsey 225.32 Disc. means shall be nearest point of entry. Coductors shall comply with 230.6. 250.32. buildings supplied by branch shall have grounding electrode.
|
ELE18-01391
| Conference | 11/7/2018 | 11/7/2018 | 11/7/2018 2:26:16 PM | P | DONE |
|
|
Call Scott for ceiling on ramp from level 1 to LL1. Rough in wall on L1 south of west elevator. Inspect grounding electrode system. Phone #: ###-#### Inspection requested via web by Tom Betty Discussed boding of Gas line.(Do not install as per. Daryl D.) Disc. ahead of fire pump controller will make it an Unreliable power source as Per NFPA 20.(will check with engineer)
|
ELE18-01391
| Electrical Rough-In | 11/6/2018 | 11/7/2018 | 11/7/2018 2:22:17 PM | P | PASS |
|
|
Call Scott for ceiling on ramp from level 1 to LL1. Rough in wall on L1 south of west elevator. Inspect grounding electrode system. Phone #: ###-#### Inspection requested via web by Tom Betty Areas listed ok to cover.
|
ELE18-03768
| Final | 11/7/2018 | 11/7/2018 | 11/7/2018 2:16:44 PM | P | PASS |
|
|
Corbin Metcalf ###-#### or Justin Metcalf ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg Final ok
|
ELE18-04180
| Permanent Service | 11/7/2018 | 11/7/2018 | 11/7/2018 12:30:44 PM | A | CANC |
|
|
|
ELE18-04299
| Temporary Service | 11/7/2018 | 11/7/2018 | 11/7/2018 11:28:57 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE18-04283
| Electrical Rough-In | 11/6/2018 | 11/7/2018 | 11/7/2018 11:28:37 AM | A | PASS |
|
|
Alan-no building permit Phone #: ###-#### Kitchen and living room wet bar only ok to cover
|
ELE18-04292
| Final | 11/6/2018 | 11/7/2018 | 11/7/2018 10:26:21 AM | A | PASS |
|
|
final and permanent service for cable t.v. power supply .alpha cabinet.located at s.e. corner of 3676 e.warm springs ave. behind fire station.contact #2088694390 Andy Phone #: ###-#### Inspection requested via web by andrew dopieralski Final ok
|
ELE18-04292
| Permanent Service | 11/7/2018 | 11/7/2018 | 11/7/2018 10:25:57 AM | P | PASS |
|
|
final and permanent service for cable t.v. power supply .alpha cabinet.located at s.e. corner of 3676 e.warm springs ave. behind fire station.contact #2088694390 Andy Phone #: ###-#### Inspection requested via web by andrew dopieralski p/s u/g n ok
|
ELE18-03774
| Rough-In Permanent Service | 11/6/2018 | 11/7/2018 | 11/7/2018 10:04:05 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson Rough in ok p/s u/g n ok
|
ELE18-03062
| Final | 11/7/2018 | 11/7/2018 | 11/7/2018 10:03:20 AM | A | PASS |
|
|
GARAGE CODE 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|
ELE18-04300
| Temporary Service | 11/7/2018 | 11/7/2018 | 11/7/2018 9:29:16 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn
|
ELE18-02216
| Electrical Rough-In | 11/6/2018 | 11/7/2018 | 11/7/2018 8:33:11 AM | A | CANC |
|
|
Thanks Phone #: ###-#### Inspection requested via web by CHRIS CARMINE
|