ELE19-01688
| Electrical Rough-In | 12/3/2019 | 12/3/2019 | 12/3/2019 2:57:36 PM | P | PASS |
|
|
Contact is Tony Holt. Underground rough-in inspection Phone #: ###-#### Inspection requested via web by Scott Campbell Duct bank on South side of building ok to cover
|
ELE19-04490
| Electrical Rough-In | 12/2/2019 | 12/3/2019 | 12/3/2019 1:15:46 PM | P | PASS |
|
|
Please call Brian Prussia with any questions or concerns at ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting listing only ok
|
ELE19-04630
| Permanent Service | 12/3/2019 | 12/3/2019 | 12/3/2019 12:24:39 PM | P | PASS |
|
|
lockbox code 2769. New panel is located downstairs off main hall in the middle of the basement. Phone #: ###-#### Inspection requested via web by Ryan Wake p/s u/g rec ok
|
ELE19-04280
| Electrical Rough-In | 12/2/2019 | 12/3/2019 | 12/3/2019 11:23:31 AM | A | FAIL |
|
|
Call 30 minutes ahead // Miles Phone #: ###-#### 314.25 All boxes shall have covers (4 j boxes 2 in breakroom 2 in offices) 300.11B Cables shall not be supported by ceiling grid. (low volt cables)
|
ELE19-03864
| Final | 12/2/2019 | 12/3/2019 | 12/3/2019 10:56:51 AM | A | PASS |
|
|
Door will be unlocked nobody lives there anymore it''s up for sale any questions please give me a call thank you. Phone #: ###-#### Inspection requested via web by David Kubik final ok
|
ELE19-03862
| Final | 12/2/2019 | 12/3/2019 | 12/3/2019 10:25:21 AM | A | PASS |
|
|
Access through side gate to back door Phone #: ###-#### Inspection requested via web by Andy Duckett Countertop in front of panel was removed at time of final. Corrections have been made final ok
|
ELE19-04563
| Final | 12/2/2019 | 12/3/2019 | 12/3/2019 10:10:27 AM | A | PASS |
|
|
Key is located in the hose bib cover in front of 2401. replaced 100 AMP panel with a new 100 AMP panel. Phone #: ###-#### Inspection requested via web by Caleb Gaylord Final ok
|
ELE19-04563
| Electrical Rough-In | 12/3/2019 | 12/3/2019 | 12/3/2019 10:10:14 AM | P | PASS |
|
|
Key is located in the hose bib cover in front of 2401. replaced 100 AMP panel with a new 100 AMP panel. Phone #: ###-#### Inspection requested via web by Caleb Gaylord Rough in ok
|
ELE19-04522
| Electrical Rough-In | 12/3/2019 | 12/3/2019 | 12/3/2019 9:40:21 AM | A | PASS |
|
|
We Would Like To Get A Cover Inspection On This Project Its Ready To Go And The Access Lock Box Code Is 1030 Thanks So Much Phone #: ###-#### Inspection requested via web by jason shifflett Kitchen, Living room wall L and R of FP., Bedrooms, Both Bathrooms ok to cover. (Recep needed to the right of Master slider before final)
|
ELE19-03021
| Permanent Service | 12/2/2019 | 12/3/2019 | 12/3/2019 9:13:54 AM | A | FAIL |
|
|
Thank you.. Phone #: ###-#### Inspection requested via web by CHRIS CARMINE 110.24 Available fault current shall be posted. 250.68A. Connection to grounding electrode shall be accessible. (Mudring needed at ufer. 250.104 A 1 Metal water piping shall be bonded(Fininsh water line connections)
|