ELE17-00559
| Electrical Rough-In | 3/8/2017 | 3/8/2017 | 3/8/2017 12:56:20 PM | P | PASS |
|
|
Tim Phone #: ###-#### North Offices only Rough in ok
|
ELE17-00533
| Final | 3/7/2017 | 3/8/2017 | 3/8/2017 12:53:59 PM | A | PASS |
|
|
Final for meter pack Final ok
|
ELE16-02440
| Final | 3/8/2017 | 3/8/2017 | 3/8/2017 12:53:35 PM | P | PASS |
|
|
Tim Phone #: ###-#### Service only Final ok
|
ELE16-02342
| Final | 3/7/2017 | 3/8/2017 | 3/8/2017 12:18:28 PM | A | PASS |
|
|
Final for service Final ok
|
ESC15-01579
| Tracking Control | 3/8/2017 | 3/8/2017 | 3/8/2017 11:52:30 AM | A | FAIL |
|
|
No track out control observed
|
ELE16-03763
| Electrical Rough-In | 3/7/2017 | 3/8/2017 | 3/8/2017 9:22:39 AM | A | PASS |
|
|
Paver grid bonding around tub Phone #: ###-#### Inspection requested via web by Lars Johnson Paver grid bond ok, Will verify pavers between fence and tub and will verify Gas fire pit.
|
ELE16-02746
| Electrical Rough-In | 3/7/2017 | 3/8/2017 | 3/8/2017 12:00:00 AM | P | FAIL |
|
|
building #2; Phone #: ###-#### 240.24 D overcurrent protection shall not be located in closets. 210.52 B 2 Small appliance circuits shall have no other outlets. Misc Recep additions and NM cable strapping. Next Inspection request needs room numbers listed.
|