Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01284 Electrical Rough-In5/13/20195/13/20195/13/2019 3:05:07 PMPPASS
Phone #: ###-#### Inspection requested via web by Steven M Bandkau Jr shop rough in ok
ELE19-01284 Permanent Service5/13/20195/13/20195/13/2019 2:50:38 PMPPASS
Phone #: ###-#### Inspection requested via web by Steven M Bandkau Jr p/s u/g n ok
ELE19-01748 Electrical Rough-In5/13/20195/13/20195/13/2019 2:24:30 PMPFAIL
Call ahead for lockbox combo - Lance ###-#### // Phone #: ###-#### Inspection requested via web by Matt Sovic 330.12 MC shall not be used where exposed to physical damage.
300.4A1 & 300.4D where ran through holes less than 1 1/4in from the face of framing member, it shall be protected.
Multiple locations through out project.
MC shall not be suppoted to the inside channel of Metal 2x4.
ELE19-01421 Final5/13/20195/13/20195/13/2019 2:09:40 PMPPASS
Ready for ceiling and final inspection Phone #: ###-#### Inspection requested via web by Kevin Oderkirk Final ok
ELE19-00768 Final5/13/20195/13/20195/13/2019 12:28:37 PMPFAIL
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk Recep above fireplace not trimmed out
ELE19-01752 Electrical Rough-In5/13/20195/13/20195/13/2019 12:11:49 PMPPASS
Lock box front door 5234 Phone #: ###-#### Inspection requested via web by John VanZandt Kitchen only ok to cover
ELE13-00545 ELE-Aging Inspection5/13/20195/13/20195/13/2019 11:00:51 AM PASS
Waiting for access
ELE15-03134 Final5/10/20195/13/20195/13/2019 10:59:27 AMAPASS
Any Questions please call Louis at ###-#### Phone #: ###-#### Inspection requested via web by Louis Keller Final ok
ELE19-01645 Rough-In Permanent Service5/10/20195/13/20195/13/2019 9:55:03 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn Check attic for device covers at final rough in ok p/s u/g n ok
ELE19-01689 Electrical Rough-In5/10/20195/13/20195/13/2019 9:34:20 AMAPASS
bonding and underground for pool // Kevin Phone #: ###-#### Underground and coner bonds around hot tub and pool ok to cover
ELE19-01663 Final5/10/20195/13/20195/13/2019 8:56:46 AMAPASS
For panel upgrade from old 70 amp Bulldog Pushmatic to a new 100 amp panel.
Please call homeowner with ETA at 2085708007. Phone #: ###-#### Inspection requested via web by Dan Hilke Final ok
ELE19-01742 Rough-In Permanent Service5/12/20195/13/20195/13/2019 8:39:10 AMAPASS
Phone #: ###-#### Inspection requested via web by Neal Rumsey rough in ok p/s u/g n ok