ELE20-01754
| Final | 5/22/2020 | 5/26/2020 | 5/26/2020 1:40:16 PM | P | PASS |
|
|
Please call Aric on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks final ok
|
ELE20-01716
| Electrical Rough-In | 5/26/2020 | 5/26/2020 | 5/26/2020 1:05:33 PM | P | NH |
|
|
Contact: Matt Beglan. Underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden No access No answer at contact number
|
ELE20-01752
| Final | 5/22/2020 | 5/26/2020 | 5/26/2020 12:54:50 PM | P | PASS |
|
|
Please call Aric on your way -###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks No work done under this permit. Contractor used existing recep for Insta hot power
|
ELE20-01573
| Electrical Rough-In | 5/26/2020 | 5/26/2020 | 5/26/2020 11:32:36 AM | P | PASS |
|
|
Taylor Barton is the onsite contact: ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting 25A breaker installed and labeled at time of rough in. listing ok
|
ELE20-01647
| Rough-In Permanent Service | 5/22/2020 | 5/26/2020 | 5/26/2020 11:05:51 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rodney Monroe Rough in ok p/s u/g n ok
|
ELE20-01755
| Electrical Rough-In | 5/22/2020 | 5/26/2020 | 5/26/2020 10:53:57 AM | A | FAIL |
|
|
Doug Phone #: ###-#### 210.11C1. 2 small appliance circuits needed.(Circuits shall serve no others. Remove lighting from dining room.)210.19A1. Brach circuit ampacity of continuous and noncontinuous loads.(Dish/ disp shall be dedicated citcuit and not fed from lighting circuit) 210.52E3. Balcony shall have recep. 110.3 B. Equipment shall be installed as per manufacturers specs.(100 amp breaker installed in Meter main on a 50amp max location. Move breaker.)
|
ELE20-01713
| Final | 5/20/2020 | 5/26/2020 | 5/26/2020 9:34:01 AM | A | PASS |
|
|
Someone will be home. If you have any questions please feel free to contact Sam ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Mini split final ok
|
ELE20-01713
| Electrical Rough-In | 5/20/2020 | 5/26/2020 | 5/26/2020 9:33:19 AM | A | PASS |
|
|
Someone will be home. If you have any questions please feel free to contact Sam ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Mini split rough in ok
|
ELE19-01688
| Conference | 5/22/2020 | 5/26/2020 | 5/26/2020 9:31:45 AM | A | PASS |
|
|
8:30 Am Consult Main hospital Phone #: ###-#### Inspection requested via web by Mark M Discussed requirments of 110.26E(1) Dedicated electrical equipment space. Water lines above equipment must be above structural ceiling to be alowed. Will build a structural soffit around lines to comply with code.
|