Inspections for the day of: Tuesday, May 26, 2020.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE20-01754 Final5/22/20205/26/20205/26/2020 1:40:16 PMPPASS
Please call Aric on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks final ok
ELE20-01716 Electrical Rough-In5/26/20205/26/20205/26/2020 1:05:33 PMPNH
Contact: Matt Beglan. Underground inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden No access No answer at contact number
ELE20-01752 Final5/22/20205/26/20205/26/2020 12:54:50 PMPPASS
Please call Aric on your way -###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks No work done under this permit. Contractor used existing recep for Insta hot power
ELE20-01573 Electrical Rough-In5/26/20205/26/20205/26/2020 11:32:36 AMPPASS
Taylor Barton is the onsite contact: ###-#### Phone #: ###-#### Inspection requested via web by BRS Permitting 25A breaker installed and labeled at time of rough in. listing ok
ELE20-01647 Rough-In Permanent Service5/22/20205/26/20205/26/2020 11:05:51 AMAPASS
Phone #: ###-#### Inspection requested via web by Rodney Monroe Rough in ok p/s u/g n ok
ELE20-01755 Electrical Rough-In5/22/20205/26/20205/26/2020 10:53:57 AMAFAIL
Doug Phone #: ###-#### 210.11C1. 2 small appliance circuits needed.(Circuits shall serve no others. Remove lighting from dining room.)210.19A1. Brach circuit ampacity of continuous and noncontinuous loads.(Dish/ disp shall be dedicated citcuit and not fed from lighting circuit) 210.52E3. Balcony shall have recep. 110.3 B. Equipment shall be installed as per manufacturers specs.(100 amp breaker installed in Meter main on a 50amp max location. Move breaker.)
ELE20-01713 Final5/20/20205/26/20205/26/2020 9:34:01 AMAPASS
Someone will be home. If you have any questions please feel free to contact Sam ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Mini split final ok
ELE20-01713 Electrical Rough-In5/20/20205/26/20205/26/2020 9:33:19 AMAPASS
Someone will be home. If you have any questions please feel free to contact Sam ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan Mini split rough in ok
ELE19-01688 Conference5/22/20205/26/20205/26/2020 9:31:45 AMAPASS
8:30 Am Consult Main hospital Phone #: ###-#### Inspection requested via web by Mark M Discussed requirments of 110.26E(1) Dedicated electrical equipment space. Water lines above equipment must be above structural ceiling to be alowed. Will build a structural soffit around lines to comply with code.