Inspections for the day of: Wednesday, June 3, 2020.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04658 Rough-In Permanent Service6/3/20206/3/20206/3/2020 2:58:23 PMPCANC
Service inspection Building #4. thank you Phone #: ###-#### Inspection requested via web by Stuart Welton
ELE19-04021 Final6/3/20206/3/20206/3/2020 2:48:22 PMPPASS
Final inspection for Building #7. Thank you Phone #: ###-#### Inspection requested via web by Stuart Welton Final ok
ELE20-01848 Temporary Service6/3/20206/3/20206/3/2020 2:25:45 PMPPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk T/s u/g n ok)
ELE20-01878 Temporary Service6/3/20206/3/20206/3/2020 2:24:58 PMPFAIL
Phone #: ###-#### Inspection requested via web by Alan Lusk 250.50 Grounding electrode required. (No ground rod)
ELE20-01413 Temporary Service6/3/20206/3/20206/3/2020 2:22:49 PMPFAIL
Phone #: ###-#### Inspection requested via web by Alan Lusk 250.50 Grounding electrode required. (No ground rod)
ELE20-01755 Permanent Service6/3/20206/3/20206/3/2020 2:10:34 PMPPASS
p/s u/g n ok
ELE20-01755 Electrical Rough-In6/2/20206/3/20206/3/2020 2:10:03 PMPPASS
Douglas Phone #: ###-#### corrections made rough in ok
ELE20-00027 Final6/3/20206/3/20206/3/2020 1:53:47 PMPPASS
door will b open or a key under bucket by front door Phone #: ###-#### Inspection requested via web by dennis mcneely Final ok
ELE19-04947 Final6/3/20206/3/20206/3/2020 1:52:56 PMPPASS
door open or key by gate fence post under rock Phone #: ###-#### Inspection requested via web by dennis mcneely Final ok
ELE20-00779 Final6/2/20206/3/20206/3/2020 12:36:17 PMPPASS
Final inspection for the B36 Tray Wash.
Contact Scott Wilson.
Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek No sign off sheet onsite final ok
ELE18-01437 Final6/2/20206/3/20206/3/2020 11:45:36 AMAFAIL
Phone #: ###-#### Inspection requested via web by Ryan Wilson 300.9 Interior of Raceways in wet locations, shall be cosidered wet location. 334.12 NM cable shall not be installed in wet location. (NM cable installed in flex from crawl to disc, and from Disc. to Condensor
ELE20-00974 Permanent Service6/2/20206/3/20206/3/2020 11:29:51 AMAFAIL
screened // Ron Phone #: ###-#### 210.11C2&210.52F 1 20A circuit shall be provided for Laundry equipment. 250.50 All Grounding electrodes preasant at a building shall be bonded together to form the grounding electrode system
ELE20-00974 Electrical Rough-In6/2/20206/3/20206/3/2020 11:27:24 AMAFAIL
screened // Ron Phone #: ###-#### 210.11C2&210.52F 1 20A circuit shall be provided for Laundry equipment. 250.50 All Grounding electrodes preasant at a building shall be bonded together to form the grounding electrode system
ELE20-00031 Final6/2/20206/3/20206/3/2020 10:45:40 AMANR
clay Phone #: ###-#### Contractor did not schedule final. Was unaware of inspection.
ELE20-00030 Final6/2/20206/3/20206/3/2020 10:44:58 AMANR
clay Phone #: ###-#### Contractor did not schedule final
ELE18-00801 Final6/2/20206/3/20206/3/2020 9:48:31 AMANH
Phone #: ###-#### Inspection requested via web by Ryan Wilson No access
ELE20-00989 Final6/2/20206/3/20206/3/2020 9:28:47 AMAPASS
Inspection requested via web by Danny Pardee Calliber collision sign only final ok
ELE20-00020 Final6/2/20206/3/20206/3/2020 9:04:52 AMAPASS
Inspection requested via web by Danny Pardee Albertson "Drive up and Go" sign only final ok
ELE20-01079 Final6/2/20206/3/20206/3/2020 8:42:37 AMAPASS
Phone #: ###-#### Inspection requested via web by Rodney Monroe corrections made final ok
ELE20-01146 Final6/2/20206/3/20206/3/2020 8:41:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Rodney Monroe corrections made final ok
ELE20-01801 Rough-In Permanent Service6/2/20206/3/20206/3/2020 5:40:15 AMACANC
Phone #: ###-#### >> Inspection requested via web by Troy Ballard Inspection cancelled from web by: Troy Ballard