ELE19-04658
| Rough-In Permanent Service | 6/3/2020 | 6/3/2020 | 6/3/2020 2:58:23 PM | P | CANC |
|
|
Service inspection Building #4. thank you Phone #: ###-#### Inspection requested via web by Stuart Welton
|
ELE19-04021
| Final | 6/3/2020 | 6/3/2020 | 6/3/2020 2:48:22 PM | P | PASS |
|
|
Final inspection for Building #7. Thank you Phone #: ###-#### Inspection requested via web by Stuart Welton Final ok
|
ELE20-01848
| Temporary Service | 6/3/2020 | 6/3/2020 | 6/3/2020 2:25:45 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk T/s u/g n ok)
|
ELE20-01878
| Temporary Service | 6/3/2020 | 6/3/2020 | 6/3/2020 2:24:58 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk 250.50 Grounding electrode required. (No ground rod)
|
ELE20-01413
| Temporary Service | 6/3/2020 | 6/3/2020 | 6/3/2020 2:22:49 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk 250.50 Grounding electrode required. (No ground rod)
|
ELE20-01755
| Permanent Service | 6/3/2020 | 6/3/2020 | 6/3/2020 2:10:34 PM | P | PASS |
|
|
p/s u/g n ok
|
ELE20-01755
| Electrical Rough-In | 6/2/2020 | 6/3/2020 | 6/3/2020 2:10:03 PM | P | PASS |
|
|
Douglas Phone #: ###-#### corrections made rough in ok
|
ELE20-00027
| Final | 6/3/2020 | 6/3/2020 | 6/3/2020 1:53:47 PM | P | PASS |
|
|
door will b open or a key under bucket by front door Phone #: ###-#### Inspection requested via web by dennis mcneely Final ok
|
ELE19-04947
| Final | 6/3/2020 | 6/3/2020 | 6/3/2020 1:52:56 PM | P | PASS |
|
|
door open or key by gate fence post under rock Phone #: ###-#### Inspection requested via web by dennis mcneely Final ok
|
ELE20-00779
| Final | 6/2/2020 | 6/3/2020 | 6/3/2020 12:36:17 PM | P | PASS |
|
|
Final inspection for the B36 Tray Wash. Contact Scott Wilson. Thank you. Phone #: ###-#### Inspection requested via web by Cathy Duchek No sign off sheet onsite final ok
|
ELE18-01437
| Final | 6/2/2020 | 6/3/2020 | 6/3/2020 11:45:36 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson 300.9 Interior of Raceways in wet locations, shall be cosidered wet location. 334.12 NM cable shall not be installed in wet location. (NM cable installed in flex from crawl to disc, and from Disc. to Condensor
|
ELE20-00974
| Permanent Service | 6/2/2020 | 6/3/2020 | 6/3/2020 11:29:51 AM | A | FAIL |
|
|
screened // Ron Phone #: ###-#### 210.11C2&210.52F 1 20A circuit shall be provided for Laundry equipment. 250.50 All Grounding electrodes preasant at a building shall be bonded together to form the grounding electrode system
|
ELE20-00974
| Electrical Rough-In | 6/2/2020 | 6/3/2020 | 6/3/2020 11:27:24 AM | A | FAIL |
|
|
screened // Ron Phone #: ###-#### 210.11C2&210.52F 1 20A circuit shall be provided for Laundry equipment. 250.50 All Grounding electrodes preasant at a building shall be bonded together to form the grounding electrode system
|
ELE20-00031
| Final | 6/2/2020 | 6/3/2020 | 6/3/2020 10:45:40 AM | A | NR |
|
|
clay Phone #: ###-#### Contractor did not schedule final. Was unaware of inspection.
|
ELE20-00030
| Final | 6/2/2020 | 6/3/2020 | 6/3/2020 10:44:58 AM | A | NR |
|
|
clay Phone #: ###-#### Contractor did not schedule final
|
ELE18-00801
| Final | 6/2/2020 | 6/3/2020 | 6/3/2020 9:48:31 AM | A | NH |
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wilson No access
|
ELE20-00989
| Final | 6/2/2020 | 6/3/2020 | 6/3/2020 9:28:47 AM | A | PASS |
|
|
Inspection requested via web by Danny Pardee Calliber collision sign only final ok
|
ELE20-00020
| Final | 6/2/2020 | 6/3/2020 | 6/3/2020 9:04:52 AM | A | PASS |
|
|
Inspection requested via web by Danny Pardee Albertson "Drive up and Go" sign only final ok
|
ELE20-01079
| Final | 6/2/2020 | 6/3/2020 | 6/3/2020 8:42:37 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rodney Monroe corrections made final ok
|
ELE20-01146
| Final | 6/2/2020 | 6/3/2020 | 6/3/2020 8:41:28 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rodney Monroe corrections made final ok
|
ELE20-01801
| Rough-In Permanent Service | 6/2/2020 | 6/3/2020 | 6/3/2020 5:40:15 AM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Troy Ballard Inspection cancelled from web by: Troy Ballard
|