ELE18-02911
| Final | 8/8/2018 | 8/9/2018 | 8/9/2018 2:22:51 PM | P | PASS |
|
|
ready for final. Homeowner said she will be home again. We hope. Her name is Diana Salzman ###-####. If having problems please call Jason at ###-####
Thanks Phone #: ###-#### Inspection requested via web by Kelly Felin final ok
|
ELE18-02166
| Final | 8/9/2018 | 8/9/2018 | 8/9/2018 1:54:47 PM | P | FAIL |
|
|
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk Garage receps dead, Down living dead, front W/P dead
|
ELE18-01647
| Electrical Rough-In | 8/9/2018 | 8/9/2018 | 8/9/2018 1:17:27 PM | P | PASS |
|
|
Wall Cover. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Area "D" rooms only ok to cover
|
ELE18-02846
| Final | 8/8/2018 | 8/9/2018 | 8/9/2018 12:43:12 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by BRS Permitting
|
ELE18-01059
| Final | 8/8/2018 | 8/9/2018 | 8/9/2018 11:46:06 AM | A | PASS |
|
|
Tim Phone #: ###-#### Final ok
|
ELE18-01391
| Electrical Rough-In | 8/9/2018 | 8/9/2018 | 8/9/2018 11:32:09 AM | A | CANC |
|
|
Call Tony for Level 1 wall rough in review. Phone #: ###-#### Inspection requested via web by Tom Betty
|
ELE18-01391
| Conference | 8/9/2018 | 8/9/2018 | 8/9/2018 11:32:00 AM | P | DONE |
|
|
Call Tony for Level 1 wall rough in review. Phone #: ###-#### Inspection requested via web by Tom Betty Discussed termination of redundant ground in connectors.(Waiting on documentation from manufacturer) Discussed conduit supports from cupplings and connectors.(358.30A Ex 1. Fastening shall be permited to be increased to 5ft where Structure does not permit 3ft) Support does not need to be within 5ft of coupling, just within 10 ft of last support as exhibit 358.1 of the 2017 NEC hand book describes.
|
ELE18-02970
| Electrical Rough-In | 8/8/2018 | 8/9/2018 | 8/9/2018 10:31:13 AM | A | PASS |
|
|
Please call 30 min out for access.
Cross street is peirce Phone #: ###-#### Inspection requested via web by William Andrews Kitchen only ok to cover
|
ELE18-03012
| Final | 8/8/2018 | 8/9/2018 | 8/9/2018 9:56:11 AM | A | FAIL |
|
|
CALL MARCUS WITH QUESTIONS ###-#### HOMEOWNER CONTACT IS PHIL AT ###-#### Phone #: ###-#### Inspection requested via web by A.M.E. Office 20amp installed. 440.22 Minimum 25amp nameplate.
|
ELE18-02955
| Rough-In Permanent Service | 8/8/2018 | 8/9/2018 | 8/9/2018 9:26:37 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough in ok p/s u/g n ok
|
ELE18-02980
| Temporary Service | 8/9/2018 | 8/9/2018 | 8/9/2018 8:58:15 AM | A | PASS |
|
|
call with any questions thank you Phone #: ###-#### Inspection requested via web by kim grundhauser t/s u/g n ok
|
ELE18-01206
| Electrical Rough-In | 8/8/2018 | 8/9/2018 | 8/9/2018 8:41:57 AM | A | PASS |
|
|
Call Chris for inspection of walls/columns on 3rd floor areas A and B. Thanks! Phone #: ###-#### Inspection requested via web by Rafael Castillo 3rd floor Shaft walls only ok to cover
|
ELE18-01647
| Electrical Rough-In | 8/8/2018 | 8/9/2018 | 8/9/2018 7:47:58 AM | A | CANC |
|
|
Wall cover. Danny is the onsite contact Phone #: ###-#### >> Inspection requested via web by Buster Bowen Inspection cancelled from web by: Buster Bowen
|