Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-00747 Electrical Rough-In3/13/20163/14/20163/14/2016 4:02:12 PMPPASS
inspection for wall cover only Phone #: ###-#### Inspection requested via web by cris flores r/i new walls and firred out exterior wall ok
ELE15-03589 Final3/14/20163/14/20163/14/2016 3:38:04 PMPPASS
Robert Phone #: ###-#### final ok
ELE15-03589 Electrical Rough-In3/14/20163/14/20163/14/2016 3:37:19 PMPPASS
Robert Phone #: ###-#### r/i ok
ELE16-00749 Permanent Service3/14/20163/14/20163/14/2016 3:14:30 PMPPASS
Phone #: ###-#### Inspection requested via web by Monica Lehman p/s o/h n ok Mounted to post that will be part of permenent garage wall
ELE16-00749 Electrical Rough-In3/14/20163/14/20163/14/2016 3:12:16 PMPPASS
Phone #: ###-#### Inspection requested via web by Monica Lehman r/i ok NOTE AJ said there will be a floor box installed at stair rail wall at final insp.
ELE15-03691 Final3/14/20163/14/20163/14/2016 2:45:05 PMPPASS
Thank you
Please call ###-#### 15 to 30 minutes prior 2 inspection. Alan will come unlock
The door Phone #: ###-#### Inspection requested via web by David McClellan corrections made final ok
ELE16-00786 Permanent Service3/14/20163/14/20163/14/2016 2:34:24 PMPPASS
Idaho Power is disconnecting the power at about 11:00 am, we should have everything moved and ready for re connection by 3:00 pm or shortly thereafter! people live in the older half so we want to have them powered back up by the close of the day! Thanks, Steve Phone #: ###-#### Inspection requested via web by Steven Meredith p/s o/h rec ok
ELE16-00529 Electrical Rough-In3/14/20163/14/20163/14/2016 2:17:50 PMPPASS
Walls, Bathroom for cover Phone #: ###-#### Inspection requested via web by Stan Woodward r/i ok bathroom walls and ceilings, all walls to the east
ELE16-00089 Conference3/10/20163/14/20163/14/2016 2:06:06 PMPDONE
Continue discussion of installation methods in parking garage area on 3rd floor with Rex. Phone #: ###-#### Inspection requested via web by Rafael Castillo Discuss "GBAD" parking structure conduit installation. All electrical conduit, enclosures, boxes and fixtures within 10 foot of outside edge of building shall have be listed raintite and be raintite application.
ELE15-01348 Conference3/14/20163/14/20163/14/2016 2:00:16 PMPDONE
Contact Tony Keen for conference on bus duct protection. Phone #: ###-#### Inspection requested via web by Tony Keen Discuss unfused buss duct running thru ceiling space in corridor in Bsmt. 230.6-Service entrance conductors shall be considered outside of a building or other structure under the following condition-Where installed within a building or other structure in a raceway that is encased in concrete or brick not less than 2 inches thick. Other option -install fused disconnect feeding buss duct.
ELE16-00179 Final3/11/20163/14/20163/14/2016 1:16:28 PMPPASS
Randy. Phone #: ###-#### Inspection requested via web by Sean DeLacy final ok
ELE15-03219 Electrical Rough-In3/14/20163/14/20163/14/2016 10:35:17 AMAPASS
Contact: Beau Cannon. - ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden r/i ok remainder of tgrid ceilings
ELE16-00594 Electrical Rough-In3/11/20163/14/20163/14/2016 9:58:29 AMAPASS
Sharon Phone #: ###-#### r/i new laundry room ok look for make up of j box in bsmt. at final insp. and green ground screw in dryer box
ELE15-03920 Final3/11/20163/14/20163/14/2016 9:43:33 AMAPASS
Replace existing pole sign with new. All primary power to remain as is Phone #: ###-#### Inspection requested via web by Ken Olsen final ok ul listed and disconnect
ELE15-03920 Electrical Rough-In3/14/20163/14/20163/14/2016 9:42:22 AMPPASS
Replace existing pole sign with new. All primary power to remain as is Phone #: ###-#### Inspection requested via web by Ken Olsen r/i ok
ELE15-03691 Final3/12/20163/14/20163/14/2016 9:32:43 AMAFAIL
Please call Alan Queen (homeowner) 15-30 minutes prior to inspection to give him time to get there to open door for inspector. His number is ###-#### Phone #: ###-#### Inspection requested via web by David McClellan 422.31-lockoff on water heater, fire caulk all holes in back, top and bottom of loadcenter in hot wall between garage and house
ELE16-00740 Rough-In Permanent Service3/14/20163/14/20163/14/2016 8:49:34 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn r/i ok p/s u/g n ok
ELE16-00739 Temporary Service3/11/20163/14/20163/14/2016 8:09:05 AMAPASS
temp pole Phone #: ###-#### Inspection requested via web by Rowdy Monroe t/s o/h n ok
ELE16-00179 Final3/10/20163/14/20163/11/2016 3:32:01 PMACANC
Randy. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Inspection cancelled from web by: Sean DeLacy