GCE14-00048
| GCE-Rough-In Permanent Service | 3/31/2014 | 3/31/2014 | 4/1/2014 9:17:09 AM | P | DONE |
|
|
(Mandatory Inspection) Eric Brown ###-#### needed rough in only
|
ELE14-00585
| Final | 3/30/2014 | 3/31/2014 | 3/31/2014 2:32:01 PM | P | PASS |
|
|
Call Chris with questions. ###-#### Phone #: ###-#### >> Inspection requested via web by Cyndi Dale final ok
|
ELE14-00628
| Temporary Service | 3/31/2014 | 3/31/2014 | 3/31/2014 2:08:21 PM | P | PASS |
|
|
Kelly Phone #: ###-#### relocated 100amp subfeed to temp. pole for construction. no need for Idaho power service on garage
|
ELE14-00760
| Temporary Service | 3/28/2014 | 3/31/2014 | 3/31/2014 1:35:42 PM | P | PASS |
|
|
I would like the temp service Inspected Monday so I can restore Power to most of the house. thanks Kevin All-Star electric Phone #: ###-#### >> Inspection requested via web by Kevin Oderkirk t/s o/h n ok temp. power to 2 existing loadcenters from temp. service ok
|
GCE14-00047
| GCE-Rough-In | 3/31/2014 | 3/31/2014 | 3/31/2014 1:01:37 PM | P | DONE |
|
|
AARON ###-#### needed perm. service
|
GCE14-00047
| GCE-Permanent Service | 3/31/2014 | 3/31/2014 | 3/31/2014 1:00:27 PM | P | PASS |
|
|
AARON ###-#### p/s o/h n ok maintain min. 3foot above residence roof!
|
GCE14-00039
| GCE-Rough-In | 3/31/2014 | 3/31/2014 | 3/31/2014 12:31:25 PM | P | CANC |
|
|
Butch ###-#### not ready rain ruined sauna tubes
|
ELE13-02083
| Electrical Rough-In | 3/28/2014 | 3/31/2014 | 3/31/2014 9:58:58 AM | A | PASS |
|
|
SE stair tower. George morris is contact ###-####. thank you. Phone #: ###-#### >> Inspection requested via web by Debby Pierce rough in decks ok to pour concrete
|
ELE14-00745
| Electrical Rough-In | 3/27/2014 | 3/31/2014 | 3/31/2014 9:26:48 AM | A | PASS |
|
|
AJ Phone #: ###-#### bathroom walls and ceiling ok to cover 1st floor
|
GCE14-00047
| GCE-Rough-In | 3/28/2014 | 3/31/2014 | 3/31/2014 9:03:13 AM | A | FAIL |
|
|
aaron ###-#### 250.52(A)(2)- bond service to building steel. 250.53(A)- grounding electrode system consisting of 2- ground rods required. 250.32(D) (2)-separate grounding electrode required for separate building consisting of more than one circuit.
|
ELE14-00534
| Electrical Rough-In | 3/29/2014 | 3/31/2014 | 3/30/2014 6:06:18 PM | P | CANC |
|
|
Cover inspection for floor heat in upstairs bathroom. Thank you!
Phone #: ###-#### >> Inspection requested via web by Adam Staigle Inspection cancelled from web by: Adam Staigle
|