Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-01327 Electrical Rough-In5/6/20165/6/20165/6/2016 4:48:10 PMPFAIL
Steve. Ceiling cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy 300.11(A)(1)-identify seismic to troffers with distinguishable tags or colored wire.
ELE16-00104 Final5/6/20165/6/20165/6/2016 4:19:30 PMPPASS
Late afternoon if possible - Jay Phone #: ###-#### final ok
ELE16-01464 Electrical Rough-In5/6/20165/6/20165/6/2016 3:26:03 PMPPASS
Approve for cover in slab. Phone #: ###-#### Inspection requested via web by Kevin Burke r/i underslab conduits and floor box ok
ELE16-00825 Final5/6/20165/6/20165/6/2016 2:23:29 PMPFAIL
Phone #: ###-#### Inspection requested via web by TOM BICANDI 225.31-separate bldg.shall have disconnect on that bldg. 422.31-fixed appliances shall have lockable disconnect if not in sight of appliance
ELE16-00823 Final5/6/20165/6/20165/6/2016 2:18:07 PMPFAIL
Phone #: ###-#### Inspection requested via web by TOM BICANDI 225.31- separate bldg. shall have disconnecting means. 422.31-fixed appliances shall have lockable disconnect if not in sight of disconnect.
ELE16-00387 Final5/6/20165/6/20165/6/2016 1:02:49 PMPPASS
Phone #: ###-#### Inspection requested via web by Ben Archibald final ok
ELE16-01080 Final5/5/20165/6/20165/6/2016 12:03:19 PMPPASS
We are requesting a final inspection for tomorrow May 6th in the afternoon. Our contact is Julian @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate corrections made final ok
ELE13-02506 ELE-Aging Inspection5/6/20165/6/20165/6/2016 11:36:11 AM DONE
too busy
ELE13-02508 ELE-Aging Inspection5/6/20165/6/20165/6/2016 11:35:39 AM DONE
too busy
ELE12-00850 ELE-Aging Inspection5/6/20165/6/20165/6/2016 11:34:58 AM DONE
too busy
ELE16-01416 Electrical Rough-In5/5/20165/6/20165/6/2016 10:03:09 AMAPASS
Pool bonding. Please arrive after 9:00 to give us time to install approved bonding clamps Phone #: ###-#### Inspection requested via web by Emmet Bushman rated clamps ok r/i bonding ok
ELE16-01183 Electrical Rough-In5/5/20165/6/20165/6/2016 9:39:30 AMAPASS
Inspect hall bath floor heat. Phone #: ###-#### Inspection requested via web by Terry Scott r/i ok
ELE16-01459 Electrical Rough-In5/5/20165/6/20165/6/2016 9:10:26 AMAPASS
PLEASE CALL WITH ANY QUESTIONS. Phone #: ###-#### Inspection requested via web by Garrett Collins r/i kitchen ok
ELE16-01405 Rough-In Permanent Service5/5/20165/6/20165/6/2016 8:54:28 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn r/i ok p/s u/g n ok
ELE16-01456 Rough-In Permanent Service5/5/20165/6/20165/6/2016 8:38:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk r/i ok p/s u/g n ok
ELE16-01398 Temporary Service5/6/20165/6/20165/6/2016 8:24:07 AMAPASS
Inspection requested via web by Alan Lusk t/s u/g n ok
ELE16-01399 Temporary Service5/6/20165/6/20165/6/2016 8:11:36 AMAPASS
Phone #: ###-#### Inspection requested via web by Alan Lusk t/s u/g n ok
ELE13-01291 ELE-Aging Inspection5/6/20165/6/20165/6/2016 7:33:13 AM DONE
still under construction
ELE16-01838 Electrical Rough-In5/6/20165/6/20165/6/2016 12:00:00 AMPPASS
Level 4 Stack 3 Lighting/Ceiling
Level 6 643, 645 Phone #: ###-#### Inspection requested via web by Tom Betty level 4 stack3 ONLY ceilings ok not ready on level 6