MEC19-03943 Final1/21/20201/21/20201/21/2020 4:10:06 PMPPASS
Call for access // Joe Phone #: ###-####- final ok
MEC20-00284 Final1/21/20201/21/20201/21/2020 3:49:04 PMPPASS
INSTALLER DAKOTA ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co locking caps ok
MEC20-00182 Rough-in1/20/20201/21/20201/21/2020 3:34:20 PMPFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak
1- supply main in attic needs to be 18" round not 16" round as ran per man j
2- need to secure w/h b vent in chase 2nd floor

left do not cover sticker
MEC20-00182 Pressure Test1/17/20201/21/20201/21/2020 3:32:42 PMPPASS
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass tagged meter location- 5lb flue pass
MEC20-00221 Rough-in1/21/20201/21/20201/21/2020 3:15:08 PMPFAIL
Phone #: ###-#### Inspection requested via web by Terek Worley
1- need to seal supply boot 1st floor at slider
2- need to fix all rips and tears in arma flex 1st and 2nd floor walls bare copper can be showing
3- need to fix 6" outside air pinched off at truss in attic above stairs
4- supply duct to master bath pinched off by hanger above door
5- need ladder provided by contractor to access furn/coil in attic
6- supply duct smashed by supply main trunk above hallway to bedroom 2 at truss

left notice front window
MEC20-00222 Rough-in1/21/20201/21/20201/21/2020 3:11:21 PMPFAIL
Phone #: ###-#### Inspection requested via web by Terek Worley
1- need ladder provided by contractor to access furn/coil in attic
2- need to fix all rips and tears in arma flex in attic
3- R/A duct needs to maintain nice radius from furnace R/A plenum to register can

left notice front window
MEC20-00221 Pressure Test1/21/20201/21/20201/21/2020 3:09:16 PMPPASS
Phone #: ###-#### Inspection requested via web by Terek Worley- 20lb gas pass tagged meter location
MEC20-00222 Pressure Test1/21/20201/21/20201/21/2020 3:08:55 PMPPASS
Phone #: ###-#### Inspection requested via web by Terek Worley- 20lb gas pass tagged meter location
MEC19-05673 Final1/15/20201/21/20201/21/2020 2:41:18 PMPPASS
Please inspect after 2 PM. He is elderly and it may take him some time to get to door. Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace only co ok
MEC20-00081 Final1/16/20201/21/20201/21/2020 2:20:17 PMPPASS
Please have inspector call Chuck the owner 15min prior to going out to home so that Chuck can meet inspector at the home. ###-#### Phone #: ###-#### Inspection requested via web by Carolyn Rudd- furnace a/c coil co locking caps ok
MEC20-00272 Final1/20/20201/21/20201/21/2020 1:59:43 PMPPASS
Please call Brett on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co locking caps ok
MEC20-00292 Final1/21/20201/21/20201/21/2020 1:29:35 PMPFAIL
PLEASE CALL OUR LEAD INSTALLER JOHNNY WHEN 30-45 MINS IN ROUTE SO HE CAN HAVE FLUE UNDER PRESSURE FOR WITNESSED WHEN YOU ARRIVE. LATER AFTERNOON IF AT ALL POSSIBLE- 3-5P Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace only co ok- flue not holding pressure- reschedule to meet when fixed and holding pressure
MEC19-04753 Final1/20/20201/21/20201/21/2020 1:04:13 PMPFAIL
Lock box code is 7777. Bj ###-#### Inspection requested via web by william kerwin
1- need duct blast and air balance report onsite
2- need approved man j onsite
3- seal exterior gas line penetrations
MEC19-04751 Final1/20/20201/21/20201/21/2020 1:03:08 PMPFAIL
Lock box 7777. Bj ###-#### Inspection requested via web by william kerwin
1- duct blast test and air balance reports onsite
2- fireplace installation instructions onsite none found
3- w/h flue needs 6" clearance to single wall pipe
4- approved man j onsite
5- seal exterior gas line penetrations
MEC19-04750 Final1/20/20201/21/20201/21/2020 1:01:24 PMPFAIL
Lockbox code 7777. Thanks BJ ###-#### Inspection requested via web by william kerwin- need fireplace installation instruction onsite none found- singke wall flue on water heater needs 6" clearance to sheetrock- need to seal exterior gas line penetrations
MEC19-05583 Rough-in1/21/20201/21/20201/21/2020 12:29:12 PMPPASS
repairs made and ready for re-inspection Call Tom with any questions ###-#### Phone #: ###-#### Inspection requested via web by Nick Drake- R/I ok- ok to cover
MEC20-00260 Rough-in1/17/20201/21/20201/21/2020 11:25:51 AMAFAIL
GARAGE CODE: 7445 Phone #: ###-#### Inspection requested via web by Kristy Watson
1- need to secure/support gas piping in attic
2- outside air needs tied into R/A plenum at furnace can not tie into R/A register can
3- missing 1 supply duct in bedroom 3 shows 2 only has 1

left notice front entry window
MEC20-00260 Pressure Test1/21/20201/21/20201/21/2020 11:23:20 AMAPASS
GARAGE CODE: 7445 Phone #: ###-#### Inspection requested via web by Kristy Watson- 20lb gas pass tagged meter location
MEC20-00256 Rough-in1/20/20201/21/20201/21/2020 11:15:57 AMAPASS
CHRISTINA ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace R/I ok
MEC20-00154 Rough-in1/17/20201/21/20201/21/2020 10:40:44 AMAPART
PLEASE CALL SHELDON 1 HR BEFORE SO HE CAN MEET YOU OUT THERE. ###-#### Phone #: ###-#### Inspection requested via web by Sheldon Lebow- fireplace R/I in living room only ok for cover- insulation shield verified in attic- need framing completed around b vent above roof and call in for inspection once framed and this will require a building permit and inspected prior to cover
MEC20-00268 Final1/20/20201/21/20201/21/2020 10:23:05 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co locking caps ok
MEC20-00238 Final1/16/20201/21/20201/21/2020 10:01:08 AMAFAIL
Daniel Phone #: ###-####- need secondary drain wet switch installed- need locking caps on a/c service ports
MEC20-00274 Final1/20/20201/21/20201/21/2020 9:31:10 AMAPASS
call Wayne before coming Phone #: ###-#### Inspection requested via web by Kim Lithander- furnace a/c coil co locking caps ok
MEC19-04713 Final1/17/20201/21/20201/21/2020 9:09:55 AMAFAIL
ac 4141 Phone #: ###-#### Inspection requested via web by Gary Reeves
1- need to seal line set penetration at a/c
2- need to fix flue on water heater china cap, needs to maintain space bent over on legs
MEC19-00926 Final1/16/20201/21/20201/21/2020 8:56:07 AMAFAIL
Inspection requested via web by Aaron Alandt
1- need to use approved ul tape on range duct and remove duct tape thats installed
2- single wall b vent on water heater needs 6" clearance to electric cord and exhaust fan or run in b vent to achieve clearance
MEC19-05583 Rough-in1/17/20201/21/20201/21/2020 8:35:43 AMAFAIL
please call Tom Thacker ###-#### Phone #: ###-#### Inspection requested via web by Nick Drake- condensate lines on mini split need ran in 3/4" pvc and barb fitting near head to make tie in
MEC19-05540 Final1/17/20201/21/20201/21/2020 8:19:13 AMAPASS
Call when on way ###-#### Stan Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace only co ok
MEC19-01168 DOC - Permit Expired1/21/20201/21/20201/21/2020 7:40:24 AMAPASS
no calls-no activity- permit expired
MEC20-00182 Rough-in1/17/20201/21/20201/20/2020 9:15:03 AMACANC
MEC AND FIREPL Phone #: ###-#### >> Inspection requested via web by Oleg Chervak Inspection cancelled from web by: Oleg Chervak