Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-04419 Final1/2/20201/3/20201/3/2020 3:49:03 PMPPASS
AC: 2018 Phone #: ###-#### Inspection requested via web by Gary Reeves- final ok
MEC19-04326 Final1/3/20201/3/20201/3/2020 3:15:43 PMPFAIL
GARAGE CD 1234 Phone #: ###-#### Inspection requested via web by Oleg Chervak
1- approved man j onsite
2- condensate to washer box needs completed
3- seal exterior gas line penetration at meter
MEC19-04327 Final1/3/20201/3/20201/3/2020 3:14:34 PMPFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak
1- seal exterior gas line penetration at meter
2- condensate to washer box needs completed
3- approved man j onsite
MEC20-00025 Final1/3/20201/3/20201/3/2020 2:57:18 PMPPASS
Please call Aleks on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace only co ok
MEC19-05755 Rough-in1/3/20201/3/20201/3/2020 2:17:49 PMPPART
Please call Ryan with questions at ###-####, we are working with the city to get our manual J approved. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- R/I will pass when gas piping is determined if needed to new dryer vent location may need to be retested if line is ran- Ryan is aware of this and will check in on this- Ok for insulation only DO NOT SHEETROCK- meter will be tagged once gas piping resolved- inert tape need installed thru wall or sleeve with pvc between stucco and piping- building inspector is aware of insulation only at this time
MEC19-04745 Final1/2/20201/3/20201/3/2020 1:31:41 PMPPASS
###-####- after 1 pm- wood fireplace insert and flue ok
MEC19-05777 Final12/30/20191/3/20201/3/2020 12:52:13 PMPPASS
Field super: Chad Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney- 20lb gas pass- unit heater ok
MEC20-00002 Rough-in1/2/20201/3/20201/3/2020 11:29:48 AMAPASS
Phone #: ###-#### Inspection requested via web by Tim Petsche- R/I ok- ok for cover- call in final when ready
MEC19-01679 Rough-in12/31/20191/3/20201/3/2020 11:11:40 AMAPART
cover and grease duct
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- 1st and 2nd layer firewrap ok- excluding hood connections- area A B and C corridirs ok for ceiling tiles- area A rms 111 110 109 ok for cover
MEC19-04327 Final1/3/20201/3/20201/3/2020 10:10:51 AMPCANC
GARAGE CD 1234 Phone #: ###-#### >> Inspection requested via web by Oleg Chervak Inspection cancelled from web by: Oleg Chervak
MEC19-04544 Final1/3/20201/3/20201/3/2020 10:10:41 AMPCANC
MEC AND FIREPL; CARAGE CD 3484 Phone #: ###-#### >> Inspection requested via web by Oleg Chervak Inspection cancelled from web by: Oleg Chervak
MEC19-04801 Final1/3/20201/3/20201/3/2020 10:02:02 AMAPASS
MEC AND FIREPL GARAGE CD 7530 Phone #: ###-#### Inspection requested via web by Oleg Chervak- final ok
MEC19-04259 Final12/31/20191/3/20201/3/2020 9:14:26 AMAFAIL
Lockbox Code: CHE
Builder ###-####
HVAC ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
1- range hood needs installed and sealed nothing installed
2- outside air in furnace closet needs insulated to R6
MEC19-05467 Final12/27/20191/3/20201/3/2020 8:32:40 AMAPASS
Please inspect in the AM and call the homeowner when on way: Lauren ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil co locking caps ok
MEC19-00597 Mec-Aging Inspection1/3/20201/3/20201/3/2020 7:46:04 AM DONE
MEC19-00597 DOC - Permit Expired1/3/20201/3/20201/3/2020 7:45:53 AMAPASS
no calls- no activity- permit expired