MEC19-04419
| Rough-in | 10/15/2019 | 10/15/2019 | 10/15/2019 3:55:04 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok- correction made
|
MEC19-04419
| Pressure Test | 10/15/2019 | 10/15/2019 | 10/15/2019 3:54:36 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Gary Reeves- already passed
|
MEC19-04402
| Final | 10/8/2019 | 10/15/2019 | 10/15/2019 3:27:05 PM | P | PASS |
|
|
Please call Carole @ ###-#### 30 min prior to arrival Phone #: ###-#### Inspection requested via web by Ashley Shoecraft- pellet stove final ok
|
MEC19-04469
| Final | 10/15/2019 | 10/15/2019 | 10/15/2019 3:14:01 PM | P | PASS |
|
|
furnace a/c coil co locking caps ok
|
MEC19-04625
| Rough-in | 10/15/2019 | 10/15/2019 | 10/15/2019 3:09:13 PM | P | PASS |
|
|
Call me at ###-#### to provide access since no one is home at this time. Phone #: ###-#### Inspection requested via web by terry Warden- ducts in attic ok- ok for insulation
|
MEC19-04579
| Final | 10/15/2019 | 10/15/2019 | 10/15/2019 2:34:22 PM | P | CANC |
|
|
Carol: ###-#### Phone #: ###-#### Inspection requested via web by Frank Marturello- per phone call to JR condenser is not set at this time- will reschedule when all items are set- need locking refrigerant caps on a/c ports at final
|
MEC19-04115
| Rough-in | 10/15/2019 | 10/15/2019 | 10/15/2019 2:32:16 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley 1- need to insulate outside air filter box to r-6 not r-4.2 2- need to remove 6" tap on R/A can and patch/seal and insulate to r-6
reinspection fee issued
|
MEC19-04091
| Pressure Test | 10/15/2019 | 10/15/2019 | 10/15/2019 2:30:43 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- already passed
|
MEC19-04091
| Rough-in | 10/15/2019 | 10/15/2019 | 10/15/2019 2:30:27 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley 1- missing transfer registers in bedroom 2 and 4 2- need to insulate outside air filter box and r/a can to r-6 3- need to finish range duct in crawl to outside on R/I inspection
left notice front window
|
MEC19-03978
| Rough-in | 10/15/2019 | 10/15/2019 | 10/15/2019 2:28:41 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- 1- need to remove 6" tap from R/A can and patch/seal and insulate to r-6 2- need to insulate outside air filter box to r-6 not r-4.2 3-need to fix all rips and tears in arma flex where bare copper can be seen in wall and attic
reinspection fee issued
|
MEC19-03978
| Pressure Test | 10/15/2019 | 10/15/2019 | 10/15/2019 2:26:06 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Terek Worley- 20lb gas pass tagged meter location
|
MEC19-04391
| Rough-in | 10/15/2019 | 10/15/2019 | 10/15/2019 1:48:08 PM | P | FAIL |
|
|
Please call James with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- 1- need to fix all rips and tears in arma flex in wall and attic 2- need to install 18" R/A in hallway per approved man j in hallway
left notice front of YMC folder
|
MEC19-04495
| Final | 10/14/2019 | 10/15/2019 | 10/15/2019 1:33:41 PM | P | PASS |
|
|
This is a Flue Pressure and Final Inspect. Please meet our installer at home at 1:30 . Contact for Right Now is Mary ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace a/c coil co locking caps ok- 5lb flue pass
|
MEC19-04465
| Final | 10/11/2019 | 10/15/2019 | 10/15/2019 1:07:10 PM | P | PASS |
|
|
please call our lead installer Brad when 30-45 mins in route so he can have flue under pressure when you arrive Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace a/c coil co locking caps ok- 5lb flue pass
|
MEC19-04582
| Pressure Test | 10/15/2019 | 10/15/2019 | 10/15/2019 12:31:38 PM | P | PASS |
|
|
Can you call Tom, at the number above, if there is another issue? Phone #: ###-#### Inspection requested via web by Nat Golden- 20lb gas pass tagged meter location
|
MEC19-02496
| Final | 10/14/2019 | 10/15/2019 | 10/15/2019 12:18:17 PM | P | PART |
|
|
Contact Ron Hughes when on your way please ###-#### Inspection requested via web by Melinda Hughes- need clarification on b vent ran above electrical panel- electrical inspector will let homeowner know on his inspection- rest is good
|
MEC19-04284
| Final | 10/14/2019 | 10/15/2019 | 10/15/2019 11:29:03 AM | A | PART |
|
|
Eric is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist- need approved mc weather tight connectors on condenser- Eric checking into this
|
MEC19-04284
| Rough-in | 10/14/2019 | 10/15/2019 | 10/15/2019 11:28:20 AM | A | PASS |
|
|
Eric is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist
|
MEC19-03908
| Final | 10/15/2019 | 10/15/2019 | 10/15/2019 11:27:51 AM | P | PART |
|
|
Dwayne Phone #: ###-#### 1- need air balance report onsite for hood and registers 2- need engineer approval on galv duct versus ss for hood exhaust 3- need to permantley tag gas line with address 4- need engineer approval on hood exhaust fan on how it will be controlled and what CFM quantity wanted 5 seal gas line pentration on roof
|
MEC19-03908
| Pressure Test | 10/15/2019 | 10/15/2019 | 10/15/2019 11:24:47 AM | P | PASS |
|
|
Dwayne Phone #: ###-####- 20lb gas pass tagged meter location
|
MEC19-04600
| Final | 10/14/2019 | 10/15/2019 | 10/15/2019 10:58:32 AM | P | PASS |
|
|
Final Inspection on GF ; AC Installation; contact Robert (QHC) @ ###-#### or Kevin (QHC) @ Phone #: ###-#### Inspection requested via web by Kevin Pratley- furnace a/c coil co locking caps ok
|
MEC19-04610
| Rough-in | 10/14/2019 | 10/15/2019 | 10/15/2019 10:56:03 AM | A | PART |
|
|
sealer inspection Phone #: ###-#### Inspection requested via web by Brandon Sorensen- approved prints onsite- seal on duct in office area ok- ok to insulate- call in another R/I inspection when unit heaters and exhaust duct completed
|
MEC19-04316
| Final | 10/15/2019 | 10/15/2019 | 10/15/2019 10:47:27 AM | A | PASS |
|
|
|
MEC19-04440
| Final | 10/14/2019 | 10/15/2019 | 10/15/2019 10:29:35 AM | P | CANC |
|
|
Please call Carrie prior to inspection. ###-#### Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette
|
MEC19-03560
| Final | 10/10/2019 | 10/15/2019 | 10/15/2019 10:10:47 AM | A | PART |
|
|
Danny ###-####, please call on the way Phone #: ###-#### Inspection requested via web by Mike Almanza- need to add one more fireplace and pay fee and call in inspection
|
MEC19-04395
| Rough-in | 10/15/2019 | 10/15/2019 | 10/15/2019 10:07:05 AM | P | PASS |
|
|
corrections made please come early afternoon, builder has called in for framing inspection as well. thank you -peter Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I ok HVAC and fireplace
|
MEC19-04607
| Pressure Test | 10/14/2019 | 10/15/2019 | 10/15/2019 9:39:51 AM | A | FAIL |
|
|
LINE IS UNDER PRESSURE AND YOU HAVE PERMISSION TO ACCESS PROPERTY TO CHECK PRESSURE TO SEE. LOCATED ON FRONT SIDE OF HOUSE. I LISTED HOMEOWNERS PHONE NUMBER- HER NAME IS JACQUE Phone #: ###-#### Inspection requested via web by Rick Montgomery- gauge wont zero out stuck- need to sleeve gas line thru metal siding and seal inside and outside of sleeve by final
|
MEC19-04466
| Final | 10/8/2019 | 10/15/2019 | 10/15/2019 9:30:44 AM | A | PASS |
|
|
please call our lead installer Brad to meet you onsite 30-45 mins and he will have flue ready and under pressure when you arrive. Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace a/c coil co locking caps ok- no flue test needed
|
MEC19-04469
| Final | 10/10/2019 | 10/15/2019 | 10/15/2019 9:10:35 AM | A | FAIL |
|
|
Please call homeowner 30 minutes in advance for access at ###-#### and call Ryan with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- need locking refrigerant caps on a/c ports- send pic for reinspect
|
MEC19-02068
| Final | 10/11/2019 | 10/15/2019 | 10/15/2019 8:55:03 AM | A | PART |
|
|
Builder Contact: Andy ###-#### HVAC Contact: Dan ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- units 105,106,205,206,305,306 107, 108, 207, 208,307 and 308 ok
|
MEC19-04575
| Final | 10/15/2019 | 10/15/2019 | 10/15/2019 8:19:27 AM | A | PASS |
|
|
|
MEC19-04575
| Pressure Test | 10/14/2019 | 10/15/2019 | 10/15/2019 8:18:10 AM | A | PASS |
|
|
Pressure gauge next to chimney on North side of house. Please call with any questions as I will not be on-site. Phone #: ###-#### Inspection requested via web by Lloyd Pierce- 20lb gas pass whole existing system- tagged meter location
|
MEC18-03928
| Mec-Aging Inspection | 10/15/2019 | 10/15/2019 | 10/15/2019 8:02:03 AM | | CANC |
|
|
|
MEC18-03928
| DOC - Permit Expired | 10/15/2019 | 10/15/2019 | 10/15/2019 8:01:56 AM | A | PASS |
|
|
no calls- no activity
|
MEC18-03964
| Mec-Aging Inspection | 10/15/2019 | 10/15/2019 | 10/15/2019 8:01:12 AM | | CANC |
|
|
|
MEC18-03964
| DOC - Permit Expired | 10/15/2019 | 10/15/2019 | 10/15/2019 8:01:06 AM | A | PASS |
|
|
no calls- no activity
|