Inspections for the day of: Thursday, October 3, 2019.
Number of inspections: 26
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-04293 Final10/2/201910/3/201910/3/2019 3:43:04 PMPPASS
Kevin ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- reduct whole house final ok
MEC19-01679 Rough-in10/2/201910/3/201910/3/2019 3:23:22 PMPPART
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- All area A seal on duct ok- ok to insulate excluding drops from RTU have not been installed will look at seal on grid inspection
MEC19-04234 Final9/26/201910/3/201910/3/2019 2:53:04 PMPPASS
INSTALLER TRAVIS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co ok
MEC19-03688 Final10/3/201910/3/201910/3/2019 2:13:02 PMPFAIL
Garage code is 2468 Inspection requested via web by JOSE DUARTE- need airbalance report onsite- need locking refrigerantcaps installed on condenser outside
MEC19-02778 Final10/3/201910/3/201910/3/2019 1:52:33 PMPPASS
fireplace final ok
MEC19-02812 Final10/2/201910/3/201910/3/2019 1:51:55 PMPPASS
Phone #: ###-#### Inspection requested via web by Bob Ferrin- final ok
MEC19-04327 Rough-in10/2/201910/3/201910/3/2019 1:18:00 PMPPASS
Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I ok
MEC19-04327 Pressure Test10/2/201910/3/201910/3/2019 1:17:48 PMPCANC
Phone #: ###-#### Inspection requested via web by Oleg Chervak- already passed
MEC19-04326 Rough-in10/2/201910/3/201910/3/2019 1:17:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I ok
MEC19-04326 Final10/2/201910/3/201910/3/2019 1:17:18 PMPCANC
Phone #: ###-#### Inspection requested via web by Oleg Chervak
MEC19-03399 Conference10/2/201910/3/201910/3/2019 12:42:10 PMPPASS
Duct Blast 12pm Phone #: ###-#### Inspection requested via web by Konrad Swartz- duct blast test pass
MEC19-03401 Conference10/2/201910/3/201910/3/2019 12:41:51 PMPPASS
Duct Blast 12pm This one has been completed but was Passed under the permit for 11253 so we need to Duct Blast with 11253 Phone #: ###-#### Inspection requested via web by Konrad Swartz- duct blast test pass
MEC19-03402 Conference10/2/201910/3/201910/3/2019 12:23:03 PMPPASS
Duct Blast 12pm Phone #: ###-#### Inspection requested via web by Konrad Swartz- duct blast test pass
MEC19-03404 Conference10/2/201910/3/201910/3/2019 12:12:31 PMPPASS
Duct Blast 12pm Phone #: ###-#### Inspection requested via web by Konrad Swartz- duct blast test pass
MEC19-04222 Final10/1/201910/3/201910/3/2019 11:48:30 AMPPASS
Please call customer when on way: Paul ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace a/c coil ducting gas piping man j co ok
MEC19-04372 Final10/2/201910/3/201910/3/2019 11:44:11 AMPPASS
Late AM or Early PM
Aleks ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
MEC19-04372 Pressure Test10/2/201910/3/201910/3/2019 11:43:49 AMPPASS
Late AM or Early PM
Aleks ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- 20lb gas pass whole systemn- tagged meter location- co ok
MEC19-03918 Pressure Test10/2/201910/3/201910/3/2019 10:22:11 AMPPASS
Gas Pressure Test; Contact Buck Cowell Phone #: ###-#### Inspection requested via web by jamie berg- 20lb gas pass- tagged meter location- ok to backfill underground gas piping
MEC19-03919 Pressure Test10/2/201910/3/201910/3/2019 10:16:16 AMPPASS
Gas Pressure Test; Contact Buck Cowell Phone #: ###-#### Inspection requested via web by jamie berg- 20lb gas pass- tagged meter location- ok to backfill underground gas pipe
MEC19-04391 Rough-in10/3/201910/3/201910/3/2019 10:05:16 AMAFAIL
Please call Ryan with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum-
1- need city approved man j onsite
2- gas test failed
3- need top seal supplu and R/A boots on all spot weld seams
4- need to seal and insulate supply reducer and insulate in attic above living room
5- need to insulate bare metal in attic on supply trunk above master bath
6- water heater flue or is it electric?

left correction notice in YMC folder on print table
MEC19-04391 Pressure Test10/3/201910/3/201910/3/2019 10:01:34 AMAFAIL
Please call Ryan with any questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- gas test failed gauge at 12 psi
MEC19-03210 Final10/2/201910/3/201910/3/2019 9:41:36 AMAPASS
KAI ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace final ok-
MEC19-00940 Mec-Aging Inspection10/3/201910/3/201910/3/2019 7:55:10 AM FAIL
inspection was cancelled by contractor and never reschedule- need to schedule inspection- permit will expire next aging if no activity
MEC18-05647 Mec-Aging Inspection10/3/201910/3/201910/3/2019 7:53:42 AM CANC
MEC18-05647 DOC - Permit Expired10/3/201910/3/201910/3/2019 7:53:34 AMAPASS
no activity- permit expired
MEC19-00945 Mec-Aging Inspection10/3/201910/3/201910/3/2019 7:52:26 AM FAIL
contractor needs to reschedule inspection when someones available no one home last time- permit will expire next aging if no activity- notice was left also on inspection