Inspections for the day of: Thursday, October 31, 2019.
Number of inspections: 35
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-04905 Final10/30/201910/31/201910/31/2019 3:40:14 PMPPASS
INSTALLER DAVID ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace only co ok
PLM19-04671 Final10/30/201910/31/201910/31/2019 3:38:03 PMPPASS
INSTALLER DAVID ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- water heater co ok
MEC19-03404 Final10/31/201910/31/201910/31/2019 2:54:20 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok- locking caps installed on a/c
MEC19-03402 Final10/31/201910/31/201910/31/2019 2:53:08 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok- locking caps installed on a/c
MEC19-03401 Final10/31/201910/31/201910/31/2019 2:52:41 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok- locking caps installed on a/c
MEC19-03400 Final10/31/201910/31/201910/31/2019 2:51:47 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok- locking caps on a/c
MEC19-03399 Final10/31/201910/31/201910/31/2019 2:50:22 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok- locking caps installed on a/c
MEC19-03398 Final10/31/201910/31/201910/31/2019 2:49:08 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok- locking caps installed on a/c
MEC19-02931 Final10/31/201910/31/201910/31/2019 2:48:40 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok- locking caps installed on a/c
MEC19-04801 Rough-in10/30/201910/31/201910/31/2019 2:12:51 PMPPASS
Phone #: ###-#### Inspection requested via web by Oleg Chervak- R/I ok on HVAC and FIREPLACE
MEC19-04883 Final10/31/201910/31/201910/31/2019 1:39:28 PMPPASS
Tanner ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace in crawl a/c coil co locking caps ok
MEC19-04817 Final10/30/201910/31/201910/31/2019 12:55:43 PMPPASS
INSTALLER TRAVIS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co gas piping flue locking caps ok
MEC19-02727 Final10/30/201910/31/201910/31/2019 11:03:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by Andrea Creek
1- need locking caps on both a/c service ports
2- need airbalance report for both units onsite none found
3- need sediment trap between gas shut off valve and furnace both units
4-water heater flue in laundry room needs 6" clearance to single wall pipe from sheetrock or install b vent
5- missing R/A grill 2nd floor hallway
MEC19-03971 Final10/30/201910/31/201910/31/2019 10:35:31 AMAPASS
PAT IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER- final ok
MEC19-04849 Rough-in10/30/201910/31/201910/31/2019 10:01:20 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kristy Watson
1- gas gauge does not zero out- replace
2- need to seal all spotwelds on all R/A and supply boots
3- man j shows 2 supply runs in bedrooms 2&3 only has one installed- need to add per man j or resubmit to city for approval as installed
4- exposed insulation on flex duct in crawl needs vapor barrier installed
5- main supply trunk in crawl pinched off due to plumbing drain at crawl entrance

left notice front window
MEC19-04849 Pressure Test10/31/201910/31/201910/31/2019 9:56:20 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kristy Watson- gauge doesnt zero out- replace
MEC19-04909 Final10/30/201910/31/201910/31/2019 9:51:45 AMACANC
This is a roof top unit Phone #: ###-#### Inspection requested via web by Aaron Toomey- per phone call not ready- need to change from single family to commerial on this permit before final inspection
MEC19-01484 Mec-Aging Inspection10/31/201910/31/201910/31/2019 9:28:02 AM CANC
talked with Mike about having GC schedule this inspection- bld has passed with out this inspection completed
MEC19-04887 Final10/30/201910/31/201910/31/2019 9:21:41 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- elecric furnace heat pump coil co locking caps ok
MEC19-03798 Final10/30/201910/31/201910/31/2019 8:53:49 AMACANC
Phone #: ###-#### >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
MEC19-03799 Final10/30/201910/31/201910/31/2019 8:53:47 AMACANC
Phone #: ###-#### >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
MEC19-03801 Final10/30/201910/31/201910/31/2019 8:53:45 AMACANC
Phone #: ###-#### >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
MEC19-04067 Final10/30/201910/31/201910/31/2019 8:53:43 AMACANC
Phone #: ###-#### >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
MEC19-04068 Final10/30/201910/31/201910/31/2019 8:53:41 AMACANC
Phone #: ###-#### >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
MEC19-04069 Final10/30/201910/31/201910/31/2019 8:53:37 AMACANC
Phone #: ###-#### >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
MEC19-04070 Final10/30/201910/31/201910/31/2019 8:53:35 AMACANC
Phone #: ###-#### >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
MEC19-04071 Final10/30/201910/31/201910/31/2019 8:53:33 AMACANC
Phone #: ###-#### >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
MEC19-04072 Final10/30/201910/31/201910/31/2019 8:53:31 AMACANC
Phone #: ###-#### >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
MEC19-04073 Final10/30/201910/31/201910/31/2019 8:53:29 AMACANC
Phone #: ###-#### >> Inspection requested via web by Konrad Swartz Inspection cancelled from web by: Konrad Swartz
MEC19-04885 Final10/30/201910/31/201910/31/2019 8:47:38 AMAFAIL
Call ahead to owner if you want, Bill @ ###-#### or Kevin (QHC) @ Phone #: ###-#### Inspection requested via web by Kevin Pratley- electric furnace coil heat pump co ok- need locking caps on a/c service ports- send pic for reinspect
MEC19-04857 Final10/30/201910/31/201910/31/2019 8:16:43 AMAFAIL
Please inspect before 9:30 Phone #: ###-#### Inspection requested via web by Mary LaFayette- need to schedule a flue test witness
MEC18-05974 Mec-Aging Inspection10/31/201910/31/201910/31/2019 7:58:44 AM CANC
MEC18-05974 DOC - Permit Expired10/31/201910/31/201910/31/2019 7:58:37 AMAPASS
no calls no activity
MEC19-01454 Mec-Aging Inspection10/31/201910/31/201910/31/2019 7:57:46 AM FAIL
contractor needs to schedule inspection no one home last time- permit will expire next aging if no activity
MEC19-03375 Final10/30/201910/31/201910/30/2019 3:23:30 PMPCANC
Mechanical Gas Fireplace Final Inspection. Manual is in kitchen drawer. Garage Code: 3162 Phone #: ###-#### Inspection requested via web by Dan Otero- completed 10-30-19