Inspections for the day of: Tuesday, October 8, 2019.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-04447 Rough-in10/8/201910/8/201910/8/2019 2:39:55 PMPPASS
Mechanical Gas Fireplace Rough-In Inspection Phone #: ###-#### Inspection requested via web by Dan Otero- Fireplace R/I ok
MEC19-03319 Final10/8/201910/8/201910/8/2019 2:05:33 PMPFAIL
Joe Phone #: ###-####- need locking caps on refrigerant ports on a/c- need to remove flex ducting on range hood and run in smooth wall pipe
MEC19-04369 Final10/7/201910/8/201910/8/2019 1:43:47 PMPPASS
installer JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co ok
MEC19-04478 Final10/8/201910/8/201910/8/2019 1:18:24 PMPPASS
furnace a/c coil co ok
MEC19-04456 Final10/4/201910/8/201910/8/2019 12:55:42 PMAPASS
Homeowner should be home her number is ###-#### with any access issues you can also call casey ( production manager) at ###-#### Phone #: ###-#### Inspection requested via web by Amanda Casper- furnace a/c coil co ok-
MEC19-04475 Final10/7/201910/8/201910/8/2019 12:32:24 PMPNH
Please call Louie on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- no one answered door- installer already left- please schedule when someones home
PLM19-04272 Water Heater Final10/7/201910/8/201910/8/2019 12:08:08 PMPPASS
Please call Craig on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- water heater co ok
MEC19-04467 Final10/7/201910/8/201910/8/2019 12:07:45 PMPPASS
Please call Craig on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace only co ok
MEC19-03841 Final10/8/201910/8/201910/8/2019 10:47:41 AMAPART
Emailing balance report to Brian. Phone #: ###-#### Inspection requested via web by Drew Tverdy- all equipment needs set into working order under class 1 hood and maintain 6" clearance on all sides of appliance and all moveable appliances tethered- need to install SS panel north end of hood- air balance report ok- still need approved plan mod drawings onsite to review them
MEC19-03443 Final10/8/201910/8/201910/8/2019 10:43:18 AMAPART
need secure all new gas piping to supports on roof- all equipment needs set into working order under class 1 hood
MEC19-04091 Rough-in10/7/201910/8/201910/8/2019 9:57:13 AMAFAIL
Please contact Project Manager Sam before inspection so that he can ensure a ladder is available (208)-###-#### Phone #: ###-#### Inspection requested via web by Terek Worley
1- missing transfer grills bedroom 2 and 4
2- range duct needs completed
3- need to insulate outside air filter box to minimum R-6

left notice front window
MEC19-04091 Pressure Test10/7/201910/8/201910/8/2019 9:55:35 AMACANC
Please contact Project Manager Sam before inspection so that he can ensure a ladder is available (208)-###-#### Phone #: ###-#### Inspection requested via web by Terek Worley- already passed gas test
MEC19-03978 Rough-in10/7/201910/8/201910/8/2019 9:55:00 AMAFAIL
Please contact Project Manager Sam before inspection so that he can ensure a ladder is available (208)-###-#### Phone #: ###-#### Inspection requested via web by Terek Worley-
1- gas gauge wont zero out
2- need to remove 6" tap from R/A can and patch and insulate
3- need to insulate outside air filter box to minimum R-6
4- need to fix rips and tears in arma flex where bare copper can be seen in wall and attic

left notice front window
MEC19-03978 Pressure Test10/7/201910/8/201910/8/2019 9:52:33 AMAFAIL
Please contact Project Manager Sam before inspection so that he can ensure a ladder is available (208)-###-#### Phone #: ###-#### Inspection requested via web by Terek Worley- gauge wont zero out
MEC19-04457 Final10/4/201910/8/201910/8/2019 9:21:25 AMAFAIL
Home owner stated they will be home. Phone #: ###-#### Inspection requested via web by Doug Turner- need uv protection on lineset outside at a/c- need locking refrierant caps installed on ports on a/c- need wet switch installed on secondary drain on pan- need to finish arma flex inside of furnace none there
MEC19-04478 Final10/7/201910/8/201910/8/2019 9:10:43 AMAFAIL
homeowner should be home his name is Andrey and his contact is ###-#### - with any issues contact Casey at ###-#### Phone #: ###-#### Inspection requested via web by Amanda Casper- furnace a/c coil co ok- need to uv protect lineset and install locking refrigerant caps on A/C outside- send pic to final out
MEC19-04333 Pressure Test10/4/201910/8/201910/8/2019 8:39:05 AMAPASS
homeowner will be home for inspector Phone #: ###-#### Inspection requested via web by Justin Osterhout- 20lb gas pass from meter to range location
MEC19-04333 Final10/8/201910/8/201910/8/2019 8:38:12 AMAPASS
homeowner will be home for inspector Phone #: ###-#### Inspection requested via web by Justin Osterhout
MEC19-00991 Mec-Aging Inspection10/8/201910/8/201910/8/2019 8:06:37 AM CANC
MEC19-00991 Final10/8/201910/8/201910/8/2019 8:06:31 AMAPASS
MEC19-04379 Final10/4/201910/8/201910/8/2019 8:06:03 AMACANC
This is a Flue Pressure and Final Inspect. Please meet our installer
at home at 9:00 AM. Contact for Right Now is Mary ###-####
Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette
MEC19-03021 Final10/7/201910/8/201910/8/2019 8:03:54 AMAPASS
VINNIE ###-####
Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace final ok
MEC19-04297 Rough-in10/7/201910/8/201910/8/2019 8:03:20 AMACANC
Francisco is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist- per phone with Francisco will reschedule