MEC19-04447
| Rough-in | 10/8/2019 | 10/8/2019 | 10/8/2019 2:39:55 PM | P | PASS |
|
|
Mechanical Gas Fireplace Rough-In Inspection Phone #: ###-#### Inspection requested via web by Dan Otero- Fireplace R/I ok
|
MEC19-03319
| Final | 10/8/2019 | 10/8/2019 | 10/8/2019 2:05:33 PM | P | FAIL |
|
|
Joe Phone #: ###-####- need locking caps on refrigerant ports on a/c- need to remove flex ducting on range hood and run in smooth wall pipe
|
MEC19-04369
| Final | 10/7/2019 | 10/8/2019 | 10/8/2019 1:43:47 PM | P | PASS |
|
|
installer JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co ok
|
MEC19-04478
| Final | 10/8/2019 | 10/8/2019 | 10/8/2019 1:18:24 PM | P | PASS |
|
|
furnace a/c coil co ok
|
MEC19-04456
| Final | 10/4/2019 | 10/8/2019 | 10/8/2019 12:55:42 PM | A | PASS |
|
|
Homeowner should be home her number is ###-#### with any access issues you can also call casey ( production manager) at ###-#### Phone #: ###-#### Inspection requested via web by Amanda Casper- furnace a/c coil co ok-
|
MEC19-04475
| Final | 10/7/2019 | 10/8/2019 | 10/8/2019 12:32:24 PM | P | NH |
|
|
Please call Louie on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- no one answered door- installer already left- please schedule when someones home
|
PLM19-04272
| Water Heater Final | 10/7/2019 | 10/8/2019 | 10/8/2019 12:08:08 PM | P | PASS |
|
|
Please call Craig on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- water heater co ok
|
MEC19-04467
| Final | 10/7/2019 | 10/8/2019 | 10/8/2019 12:07:45 PM | P | PASS |
|
|
Please call Craig on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- furnace only co ok
|
MEC19-03841
| Final | 10/8/2019 | 10/8/2019 | 10/8/2019 10:47:41 AM | A | PART |
|
|
Emailing balance report to Brian. Phone #: ###-#### Inspection requested via web by Drew Tverdy- all equipment needs set into working order under class 1 hood and maintain 6" clearance on all sides of appliance and all moveable appliances tethered- need to install SS panel north end of hood- air balance report ok- still need approved plan mod drawings onsite to review them
|
MEC19-03443
| Final | 10/8/2019 | 10/8/2019 | 10/8/2019 10:43:18 AM | A | PART |
|
|
need secure all new gas piping to supports on roof- all equipment needs set into working order under class 1 hood
|
MEC19-04091
| Rough-in | 10/7/2019 | 10/8/2019 | 10/8/2019 9:57:13 AM | A | FAIL |
|
|
Please contact Project Manager Sam before inspection so that he can ensure a ladder is available (208)-###-#### Phone #: ###-#### Inspection requested via web by Terek Worley 1- missing transfer grills bedroom 2 and 4 2- range duct needs completed 3- need to insulate outside air filter box to minimum R-6
left notice front window
|
MEC19-04091
| Pressure Test | 10/7/2019 | 10/8/2019 | 10/8/2019 9:55:35 AM | A | CANC |
|
|
Please contact Project Manager Sam before inspection so that he can ensure a ladder is available (208)-###-#### Phone #: ###-#### Inspection requested via web by Terek Worley- already passed gas test
|
MEC19-03978
| Rough-in | 10/7/2019 | 10/8/2019 | 10/8/2019 9:55:00 AM | A | FAIL |
|
|
Please contact Project Manager Sam before inspection so that he can ensure a ladder is available (208)-###-#### Phone #: ###-#### Inspection requested via web by Terek Worley- 1- gas gauge wont zero out 2- need to remove 6" tap from R/A can and patch and insulate 3- need to insulate outside air filter box to minimum R-6 4- need to fix rips and tears in arma flex where bare copper can be seen in wall and attic
left notice front window
|
MEC19-03978
| Pressure Test | 10/7/2019 | 10/8/2019 | 10/8/2019 9:52:33 AM | A | FAIL |
|
|
Please contact Project Manager Sam before inspection so that he can ensure a ladder is available (208)-###-#### Phone #: ###-#### Inspection requested via web by Terek Worley- gauge wont zero out
|
MEC19-04457
| Final | 10/4/2019 | 10/8/2019 | 10/8/2019 9:21:25 AM | A | FAIL |
|
|
Home owner stated they will be home. Phone #: ###-#### Inspection requested via web by Doug Turner- need uv protection on lineset outside at a/c- need locking refrierant caps installed on ports on a/c- need wet switch installed on secondary drain on pan- need to finish arma flex inside of furnace none there
|
MEC19-04478
| Final | 10/7/2019 | 10/8/2019 | 10/8/2019 9:10:43 AM | A | FAIL |
|
|
homeowner should be home his name is Andrey and his contact is ###-#### - with any issues contact Casey at ###-#### Phone #: ###-#### Inspection requested via web by Amanda Casper- furnace a/c coil co ok- need to uv protect lineset and install locking refrigerant caps on A/C outside- send pic to final out
|
MEC19-04333
| Pressure Test | 10/4/2019 | 10/8/2019 | 10/8/2019 8:39:05 AM | A | PASS |
|
|
homeowner will be home for inspector Phone #: ###-#### Inspection requested via web by Justin Osterhout- 20lb gas pass from meter to range location
|
MEC19-04333
| Final | 10/8/2019 | 10/8/2019 | 10/8/2019 8:38:12 AM | A | PASS |
|
|
homeowner will be home for inspector Phone #: ###-#### Inspection requested via web by Justin Osterhout
|
MEC19-00991
| Mec-Aging Inspection | 10/8/2019 | 10/8/2019 | 10/8/2019 8:06:37 AM | | CANC |
|
|
|
MEC19-00991
| Final | 10/8/2019 | 10/8/2019 | 10/8/2019 8:06:31 AM | A | PASS |
|
|
|
MEC19-04379
| Final | 10/4/2019 | 10/8/2019 | 10/8/2019 8:06:03 AM | A | CANC |
|
|
This is a Flue Pressure and Final Inspect. Please meet our installer at home at 9:00 AM. Contact for Right Now is Mary ###-#### Phone #: ###-#### >> Inspection requested via web by Mary LaFayette Inspection cancelled from web by: Mary LaFayette
|
MEC19-03021
| Final | 10/7/2019 | 10/8/2019 | 10/8/2019 8:03:54 AM | A | PASS |
|
|
VINNIE ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fireplace final ok
|
MEC19-04297
| Rough-in | 10/7/2019 | 10/8/2019 | 10/8/2019 8:03:20 AM | A | CANC |
|
|
Francisco is the contact. Phone #: ###-#### Inspection requested via web by stan lillquist- per phone with Francisco will reschedule
|