Inspections for the day of: Monday, November 25, 2019.
Number of inspections: 23
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-05281 Final11/25/201911/25/201911/25/2019 3:33:36 PMPPASS
Please call Paul prior to inspection. ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- electric furnace coil only ok
MEC19-05339 Final11/25/201911/25/201911/25/2019 3:11:03 PMPNH
BJ ###-####. Home is open, workers present floor is opened up in the laundry room Inspection requested via web by william kerwin- no one onsite- house locked up
MEC19-05317 Final11/22/201911/25/201911/25/2019 2:43:46 PMPPASS
Same day Install. Will not be ready for inspection until the afternoon. Please call Michael, technician on site, to ensure job is ready. If you run into any issues, call Alyssa at ###-####.
Contact Name: Michael
Contact Phone:###-#### Phone #: ###-#### Inspection requested via web by Alyssa Cromwell- furnace only co ok
MEC19-05263 Pressure Test11/25/201911/25/201911/25/2019 2:19:49 PMPPASS
Tim Phone #: ###-####- 20lb gas pass- will need access door installed in ceiling by final to access main gas shutoff valve- all 4 shutoff valves will need sediment traps installed after shut offs and before appliances- equipment may need tethers by final also
MEC19-05146 Rough-in11/25/201911/25/201911/25/2019 2:00:59 PMPFAIL
Approved Man J is now on site Phone #: ###-#### Inspection requested via web by Randy Hart- b vent appears to have screw thru it- verify and replace if needed thru roof- need to seal all spotwelds on supply and return air boots some are missing seal
MEC19-05325 Rough-in11/24/201911/25/201911/25/2019 1:25:08 PMPPASS
Phone #: ###-#### Inspection requested via web by JOSE DUARTE- R/I ok
MEC19-05325 Pressure Test11/24/201911/25/201911/25/2019 1:24:04 PMPPASS
Phone #: ###-#### Inspection requested via web by JOSE DUARTE- 20lb gas pass ragged meter location
MEC19-05326 Rough-in11/24/201911/25/201911/25/2019 12:50:56 PMPFAIL
Phone #: ###-#### Inspection requested via web by JOSE DUARTE
1- all rips and tears in arma flex need repaired in wall and attic
2- b vent thru garage wall needs insulation shield
3- need to support range duct in attic
4- dryer duct needs nail plates at ceiling
5- condensate drain does not have grade to washer box is trapped in attic

left notice
MEC19-05326 Pressure Test11/24/201911/25/201911/25/2019 12:48:19 PMPPASS
Phone #: ###-#### Inspection requested via web by JOSE DUARTE- 20lb gas pass tagged meter location
MEC19-04464 Final11/24/201911/25/201911/25/2019 12:28:56 PMPPASS
Garage code is 2468 Phone #: ###-#### Inspection requested via web by JOSE DUARTE
MEC19-05085 Final11/22/201911/25/201911/25/2019 11:32:42 AMAPASS
This is a Flue Pressure and Final Inspect. Please meet our installer
at home at 11:30. Contact for Right Now is Mary ###-####
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace only co ok- 5lb flue pass
MEC19-05224 Final11/19/201911/25/201911/25/2019 11:00:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- electric furnacer coil heat pump co locking caps ok
MEC19-05146 Rough-in11/22/201911/25/201911/25/2019 10:36:59 AMAFAIL
Reinspect Phone #: ###-#### Inspection requested via web by Randy Hart- need city approved man j onsite- need to seal all spotwelds on register boots
MEC19-05146 Pressure Test11/22/201911/25/201911/25/2019 10:36:13 AMAPASS
Reinspect Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass tagghed meter location- 5lb flue pass
MEC19-05315 Pressure Test11/22/201911/25/201911/25/2019 10:15:21 AMANH
Pressure test and fireplace. Call prior to arrival. Phone #: ###-#### Inspection requested via web by Jamee Shoecraft- no one available for inspection per phone call- I rescheduled for tomorrow am per phone call
MEC19-02561 Rough-in11/22/201911/25/201911/25/2019 10:05:50 AMAPART
Roger Graves is the job site contact ###-#### Phone #: ###-#### Inspection requested via web by Doug Madsen- seal on all ducting ok- need to finish insulation on all ducting above hard lids- all register cans need installed in bathrooms and flex for hard lid cover- call in R/I inspection when these are completed- need engineer approval on galv duct for class 2 hood shows to run in aluminum
MEC19-05049 Final11/22/201911/25/201911/25/2019 9:44:16 AMAFAIL
CALL WHEN ON THE WAY Phone #: ###-#### Inspection requested via web by Ashley Shoecraft- need flue supported on roof
MEC19-04381 Final11/21/201911/25/201911/25/2019 9:16:42 AMAFAIL
Please have inspector call Joe when in route to his home. ###-#### Phone #: ###-#### Inspection requested via web by Carolyn Rudd- need to schedule flue test for witness- service ports on a/c needs locking caps
MEC19-05319 Final11/22/201911/25/201911/25/2019 9:02:31 AMAPASS
Call 30 minutes prior to arriving for inspection so I can make sure to be there to open door. Phone #: ###-#### Inspection requested via web by marco gomez- furnace gas piping co ok
MEC19-05319 Pressure Test11/25/201911/25/201911/25/2019 9:02:02 AMAPASS
Call 30 minutes prior to arriving for inspection so I can make sure to be there to open door. Phone #: ###-#### Inspection requested via web by marco gomez- 20lb gas pass tagged meter location
MEC19-04335 Rough-in11/25/201911/25/201911/25/2019 8:47:35 AMAPASS
2 fire smoke damper clearances ok-
MEC19-05113 Rough-in11/21/201911/25/201911/25/2019 8:46:44 AMAPASS
Secondary light test of grease duct after installation on jobsite. Phone #: ###-#### Inspection requested via web by Stephen Lee- light test pass ok for firewrap
MEC19-01834 Mec-Aging Inspection11/25/201911/25/201911/25/2019 8:11:36 AM FAIL
needs called in for final inspection- permit will expire next aging if no activity