Inspections for the day of: Wednesday, November 27, 2019.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-01679 Rough-in11/26/201911/27/201911/27/2019 3:30:14 PMPPART
Phone #: ###-#### Inspection requested via web by Amanda Farnsworth- area D rms D109 and D105 seal on duct ok- ok for insulation- area B classrooms only and rms B112 and B113 ok for ceiling tile cover- 2 fire/smoke dampers need framing and sheetrock clearances per installation instructions- framing missing on sides- access doors need installed on 2 fire/smoke damper above hard lids- call in for inspection when ready
MEC19-01662 Pressure Test11/27/201911/27/201911/27/2019 3:06:46 PMPPASS
20lb gas pass to dishwasher- ok to cover walls
MEC19-05146 Rough-in11/26/201911/27/201911/27/2019 2:40:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Randy Hart- R/I ok
MEC19-04221 Rough-in11/26/201911/27/201911/27/2019 1:41:28 PMPPASS
Phone #: ###-#### Inspection requested via web by Debbie Marino- HVAC and fireplace R/I ok
MEC19-05359 Final11/26/201911/27/201911/27/2019 1:12:01 PMPPASS
Please call Dan on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- unit heater install ok
MEC19-03794 Conference11/22/201911/27/201911/27/2019 12:17:34 PMPPASS
Duct Blast 12-12:30 Phone #: ###-#### Inspection requested via web by Konrad Swartz- duct blast test pass- need to verify back draft dampers are installed on outside air by final
MEC19-03795 Conference11/22/201911/27/201911/27/2019 12:12:46 PMPPASS
Duct Blast 12-12:30 Phone #: ###-#### Inspection requested via web by Konrad Swartz- duct blast test pass- need to verify back draft dampers are installed in outside air by final
MEC19-03796 Conference11/22/201911/27/201911/27/2019 12:00:04 PMPPASS
Duct Blast 12-12:30 Phone #: ###-#### Inspection requested via web by Konrad Swartz- duct blast test pass
MEC19-04309 Final11/27/201911/27/201911/27/2019 11:59:09 AMAPASS
electrical permit issued
MEC19-03455 Final11/27/201911/27/201911/27/2019 11:57:33 AMAPASS
should have finaled on pressure test
MEC19-05049 Final11/27/201911/27/201911/27/2019 11:55:07 AMAPASS
wood fireplace final ok
MEC19-04885 Final11/27/201911/27/201911/27/2019 11:32:32 AMAPASS
locking caps installed- final ok
MEC19-04956 Rough-in11/26/201911/27/201911/27/2019 11:16:43 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kristy Watson
1- missing supply duct for hallway bath south side of home per man j
2- 6" outside air can not come from R/A can needs tied into plenum at furnace
3- approved drawings show gas fireplace no gas stub out found- need to verify fireplace

left notice front door
MEC19-04956 Pressure Test11/26/201911/27/201911/27/2019 11:14:44 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kristy Watson
1-20lb gas pressure test passes for what gas line installed but prints show gas fireplace and no stub out is found- please verify if its getting gas fireplace and fireplace would need permitted- wont tag meter location until resolved
MEC19-05296 Rough-in11/26/201911/27/201911/27/2019 10:32:09 AMAPASS
Please call Mike 1 / 2 hr. before arrival - ###-#### Phone #: ###-#### Inspection requested via web by Bryan Palmer- R/I ok- still need to add dryer duct and bath fan to permit and pay fees by final- utility rm and family room will be installed with cabinet guys for routing- will need duct blast and air balance by final
MEC19-05300 Final11/26/201911/27/201911/27/2019 9:38:21 AMAPASS
please call Mike when in route so that he can be onsite for you. Phone #: ###-#### Inspection requested via web by Yvonne Bowman- electric RTU final ok
MEC19-03644 Rough-in11/26/201911/27/201911/27/2019 9:13:46 AMAPASS
Please call when on your way to house. Phone #: ###-#### Inspection requested via web by JEFFREY DAVIS- R/I ok on range duct R/A duct bath fan and fryer duct- homeowner will be installing gas thru crawl at later date nothing in walls stub up for range and future furnace
MEC19-04610 Rough-in11/26/201911/27/201911/27/2019 8:43:30 AMAPART
cover inspection Phone #: ###-#### Inspection requested via web by Brandon Sorensen- registers flex and insulation ok on ducting installed- still need to see square to rounds insulated completely- will send pic then ok for cover of ceiling
MEC19-00273 Mec-Aging Inspection11/27/201911/27/201911/27/2019 8:27:05 AM CANC
MEC19-00273 DOC - Permit Expired11/27/201911/27/201911/27/2019 8:26:59 AMAPASS
no calls- no activity- permit expired
MEC19-02010 Mec-Aging Inspection11/27/201911/27/201911/27/2019 8:26:20 AM FAIL
contractor needs to reschedule inspection no one home last time- permit will expire next aging if no activity