Inspections for the day of: Tuesday, November 6, 2018.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-05156 Pressure Test11/5/201811/6/201811/6/2018 2:05:33 PMPPASS
Please have inspector call the installer Matt when in route to home for gas pressure test ###-#### Phone #: ###-#### Inspection requested via web by Carolyn Rudd- 20lb gas pass whole existing system- tagged gas piping at meter bar location-
MEC18-05279 Final11/6/201811/6/201811/6/2018 1:41:17 PMPPASS
Phone #: ###-#### Inspection requested via web by Justin Osterhout- furnace only co ok
MEC18-04831 Rough-in11/6/201811/6/201811/6/2018 1:14:51 PMPFAIL
Dorthy Phone #: ###-####- range hood ducting correction not made (IRC 1503.1)- remove crimped oval 90 degree and smashed 6" 90 degree and reroute both units- reinspection fee issued
MEC18-04831 Pressure Test11/6/201811/6/201811/6/2018 1:14:03 PMPCANC
Dorthy Phone #: ###-####- already passed
MEC18-04832 Rough-in11/6/201811/6/201811/6/2018 1:10:00 PMPPASS
Dorthy Phone #: ###-####- R/I ok- corrections made
MEC18-05284 Rough-in11/5/201811/6/201811/6/2018 11:23:34 AMAPART
Hard Lid for Faith Christian Center - Please call Mike Dominguez with any questions ###-#### Phone #: ###-#### Inspection requested via web by Heather Gransbery- seal and insulation on ducts in hard lid areas only ok for cover
MEC18-04557 Final11/5/201811/6/201811/6/2018 10:38:33 AMAPART
Mechanical Final needed for Lifetime AM preferred if you have any questions contact Karl at ###-#### Phone #: ###-#### Inspection requested via web by Karl Hestekin- need air balance report on EF 2 part of CO detection system- grid ceiling registers and flex all good- ok to cover- need relief damper completed and operational- need RTU 1E condensate drain installed- temp occupancy
MEC18-05298 Pressure Test11/5/201811/6/201811/6/2018 10:01:03 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- 20lb gas pass from meter to furnace location- need to straighten gas piping in closet- need to seal outdoors gas piping penetration and make sure has inert tape on it- will need combustion air in closet and b vent will need a insulation shield in attic
MEC18-05255 Final11/6/201811/6/201811/6/2018 9:16:10 AMACANC
please call so we can meet you there for the pressure test Phone #: ###-#### Inspection requested via web by Marisa Hone
MEC18-05255 Pressure Test11/6/201811/6/201811/6/2018 9:16:01 AMAFAIL
please call so we can meet you there for the pressure test Phone #: ###-#### Inspection requested via web by Marisa Hone- flue wont hold pressure- recall in when fixed and schedule time with me to meet
MEC17-05104 Mec-Aging Inspection11/6/201811/6/201811/6/2018 8:27:53 AM FAIL
still need contractor to schedule inspection
MEC18-03097 Pressure Test11/5/201811/6/201811/6/2018 8:27:17 AMAPART
60lb pressure test gauge on roof- ###-####- 60lb gas test from roof to mech room- need to retest whole system once gas has extended to meter after core drill is done
MEC18-05312 Pressure Test11/5/201811/6/201811/6/2018 7:42:11 AMPCANC
Please call Chuck prior to arrival ###-#### >> Inspection requested via web by Arielle Hendricks Inspection cancelled from web by: Arielle Hendricks
MEC18-03097 Conference11/5/201811/6/201811/5/2018 12:59:13 PMACANC
pressure test- 208- ###-####- scheduled for conference not pressure test