Inspections for the day of: Monday, December 16, 2019.
Number of inspections: 31
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-05652 Final12/16/201912/16/201912/16/2019 3:40:20 PMPPASS
CALL JOE PRIOR TO ARRIVAL Phone #: ###-#### Inspection requested via web by Jamee Shoecraft- R/I ok- final ok
MEC19-03244 Final12/16/201912/16/201912/16/2019 3:14:06 PMPPASS
Charlie Phone #: ###-####- final ok- card signed
MEC19-05352 Final12/13/201912/16/201912/16/2019 2:51:19 PMPPASS
El-Ada #A-10755; Sarah Bowman Phone #: ###-#### Inspection requested via web by Loren Bailey- furnace a/c coil co locking caps ok
MEC19-05626 Final12/13/201912/16/201912/16/2019 2:22:35 PMPPASS
INSTALLER DUSTIN ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace only 5lb flue pass co ok
MEC19-05645 Pressure Test12/16/201912/16/201912/16/2019 1:54:29 PMPFAIL
Please call homeowner 30 minutes in advance for access at ###-#### and call Eddie with questions at ###-####. Thank you Phone #: ###-#### Inspection requested via web by Rhonda Marcum- gauge at zero- need to add second shutoff valve in water heater closet after drip leg and leave drip leg open- at no time can air be on onside of valve and gas on other has to have 2 shut off valves with open tee between them- will need co detectors installed also near bedrooms- make sure gauge zeros out too
MEC19-05521 Rough-in12/13/201912/16/201912/16/2019 1:23:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok
MEC19-05521 Pressure Test12/13/201912/16/201912/16/2019 1:22:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass tagged meter location- 5lb flue pass
MEC19-03801 Final12/16/201912/16/201912/16/2019 12:18:06 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok
MEC19-03799 Final12/16/201912/16/201912/16/2019 12:17:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok
MEC19-03798 Final12/16/201912/16/201912/16/2019 12:17:19 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok
MEC19-03797 Final12/16/201912/16/201912/16/2019 12:17:05 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok
MEC19-03796 Final12/16/201912/16/201912/16/2019 12:16:50 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok
MEC19-03795 Final12/16/201912/16/201912/16/2019 12:16:35 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok
MEC19-03794 Final12/16/201912/16/201912/16/2019 12:16:18 PMPPASS
Phone #: ###-#### Inspection requested via web by Konrad Swartz- final ok
MEC19-04069 Conference12/13/201912/16/201912/16/2019 12:16:04 PMPPASS
Duct Blast Witness 12:00 PM Phone #: ###-#### Inspection requested via web by Konrad Swartz- duct blast test pass
MEC19-04068 Conference12/13/201912/16/201912/16/2019 12:10:52 PMPPASS
Duct Blast Witness 12:00 PM Phone #: ###-#### Inspection requested via web by Konrad Swartz- duct blast test pass
MEC19-04067 Conference12/13/201912/16/201912/16/2019 12:02:25 PMPPASS
Duct Blast Witness 12:00 PM Phone #: ###-#### Inspection requested via web by Konrad Swartz- duct blast test pass
MEC19-05635 Rough-in12/16/201912/16/201912/16/2019 11:31:07 AMPPASS
Phone #: ###-#### Inspection requested via web by JOSE DUARTE- R/I ok
MEC19-05636 Rough-in12/13/201912/16/201912/16/2019 11:20:34 AMAPASS
Albert Phone #: ###-####- R/I ok
MEC19-05636 Pressure Test12/13/201912/16/201912/16/2019 11:19:51 AMAPASS
Albert Phone #: ###-####- 20lb gas pass tagged meter location
MEC19-03846 Final12/13/201912/16/201912/16/2019 10:56:51 AMAFAIL
Please call technician Cody to meet you over there ###-#### Phone #: ###-#### Inspection requested via web by Nick Drake- regualtors need shut off valve before reg and drip legs installed- garage needs regulator installed
MEC19-04175 Final12/16/201912/16/201912/16/2019 10:55:50 AMAFAIL
need locking caps on a/c service ports on a/c- R/I on range duct exhaust fan and dryer duct ok
MEC19-05113 Final12/13/201912/16/201912/16/2019 9:49:55 AMAPASS
Copy of air balance report will be onsite. Phone #: ###-#### Inspection requested via web by Stephen Lee- final ok- airbalance on hood ok- clearances on equipment ok- card signed
MEC19-04335 Final12/13/201912/16/201912/16/2019 9:49:38 AMAPASS
Inspection requested via web by jeff jedlick- final ok - card signed
MEC19-05254 Final12/13/201912/16/201912/16/2019 9:31:16 AMAPASS
Inspection requested via web by Lindsey Stegemann- fireplace insert final ok
MEC19-05640 Final12/16/201912/16/201912/16/2019 9:31:15 AMAPASS
MEC19-05640 Final12/16/201912/16/201912/16/2019 9:30:32 AMAPASS
MEC19-05640 Pressure Test12/13/201912/16/201912/16/2019 9:27:40 AMAPASS
Call prior to arrival Phone #: ###-#### Inspection requested via web by Jamee Shoecraft- 20lb gas pass
MEC19-05630 Rough-in12/13/201912/16/201912/16/2019 9:03:13 AMAPASS
Someone will be there monday morning, please call Chris if you have any questions about the installation, ###-#### Phone #: ###-#### Inspection requested via web by Brett Shannon- R/I ok on range duct and bath exhaust- call in final when range hood installed
MEC19-03009 Final12/12/201912/16/201912/16/2019 8:46:24 AMAFAIL
need a duct blast witness at 9am Phone #: ###-#### Inspection requested via web by Gary Reeves- R/A plenum needs insulated to R-6 in garage- tape over bare metal all needs to maintain 75% value of insulation
MEC19-03009 Conference12/16/201912/16/201912/16/2019 8:45:21 AMAPASS
need a duct blast witness at 9am Phone #: ###-#### Inspection requested via web by Gary Reeves- duct blast test pass