Inspections for the day of: Monday, December 17, 2018.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-05963 Final12/17/201812/17/201812/17/2018 4:11:05 PMPPASS
furnace co ok
MEC18-04970 Final12/14/201812/17/201812/17/2018 3:42:52 PMPPART
Request for Final inspection. Please contact Chris, ###-####, with any questions or concerns. Inspection requested via web by Heather Gransbery- temp occupancy ok- still need engineers approval on cassette ductless minisplit that was installed instead of FCU that was ommitted from engineer- rest is good
MEC18-03171 Final12/12/201812/17/201812/17/2018 3:23:17 PMPPASS
Please call Dennis at ###-#### before going to job site. Phone #: ###-#### Inspection requested via web by Dennis Fox- final ok
MEC18-05914 Final12/13/201812/17/201812/17/2018 2:55:11 PMPPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- electric air handler ok
MEC18-05452 Final12/17/201812/17/201812/17/2018 2:01:09 PMPPASS
call ed from strite to meet inspector at jobsite 20 min in advance
thanks! Phone #: ###-#### Inspection requested via web by Manuel Canto- range hood gas piping co ok
MEC18-05892 Final12/17/201812/17/201812/17/2018 1:50:12 PMPCANC
Call owner Paul Nelson ahead of time so he can meet you there. Phone #: ###-#### Inspection requested via web by Jamee Shoecraft- per phone call with Kevin
MEC18-05050 Final12/14/201812/17/201812/17/2018 1:17:58 PMPFAIL
Garage Code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- need access into house all doors locked up garage code worked- need 3 screws in water heater flue to china cap in garage- need to seal lineset penetration outside at a/c location-
MEC18-05982 Rough-in12/14/201812/17/201812/17/2018 11:16:00 AMAFAIL
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- need approved stamped man j onsite for inspection- need to mastic/seal inside all boots supply and return- water heater b vent needs 1" clearance to truss in attic- square supply duct nw room needs insulated on square to round end cap in attic- need ladder provided to access furnace and coil in attic- need to support dryer duct every 4'- need to fix all rips and tears in arma flex whole lineset- who installed fireplace? if you did please add to description on notes- need another strap on supply duct in hallway from garage register is sagging- left correction notice front entry window
MEC18-05982 Pressure Test12/14/201812/17/201812/17/2018 11:09:32 AMAFAIL
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- gauge below 20psi
MEC18-05284 Rough-in12/17/201812/17/201812/17/2018 11:00:17 AMAPART
need to seal misc 90 degree fittings- need to insulate all supply and R/A ducts above grid ceilings- will look at when grids installed
MEC18-05284 Pressure Test12/17/201812/17/201812/17/2018 10:56:23 AMPPASS
Gas pressure 60lbs for Christian Faith. Please call Mike Dominguez ###-####. Phone #: ###-#### Inspection requested via web by Heather Gransbery- 60lb gas pass whole system- need to secure gas line to roof supports by final
MEC18-03406 Final12/14/201812/17/201812/17/2018 10:21:29 AMAPASS
Please contact Rich Beckstead (###-####) if you have any questions. Phone #: ###-#### Inspection requested via web by Beka Hereau- final ok- card signed
MEC18-00852 Final12/14/201812/17/201812/17/2018 10:21:01 AMAPASS
RUSSELL IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER- final ok- card signed
MEC17-03751 Final12/16/201812/17/201812/17/2018 9:51:50 AMAPASS
Phone #: ###-#### Inspection requested via web by Becky Granden- final ok
MEC18-05938 Final12/13/201812/17/201812/17/2018 9:12:33 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace co ok
MEC18-05950 Final12/13/201812/17/201812/17/2018 8:45:21 AMAFAIL
Phone #: ###-#### Inspection requested via web by Mary LaFayette- need furnace on/off switch for power installed in closet at furnace location
MEC18-00547 Mec-Aging Inspection12/17/201812/17/201812/17/2018 7:57:41 AM CANC
WIP