Inspections for the day of: Monday, February 25, 2019.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-05671 Final2/25/20192/25/20192/25/2019 3:21:52 PMPPASS
Requesting a final inspection. Tim will be onsite and available to meet with the inspector. He can be reached at ###-#### Phone #: ###-#### Inspection requested via web by Aaron Whiteley- final ok- no card onsite to sign
MEC19-00337 Rough-in2/22/20192/25/20192/25/2019 1:51:28 PMPFAIL
Phone #: ###-#### Inspection requested via web by Arcadio Martinez-
1) need to seal all register boots to floor 1st floor only
2) still need supply trunk on crawl completed to supply plenum drop and insulated
3) need 1" clearance to b vent at roof and draft stop in chase 2nd floor needs to be completed fully to all sides where no insulation can fall into chase
4) line set needs ran on rough in

left correction notice front window/ no equipment set
MEC19-00799 Final2/22/20192/25/20192/25/2019 1:07:50 PMPNH
Please inspect early PM. Call Joseph on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
MEC19-00733 Rough-in2/19/20192/25/20192/25/2019 11:26:07 AMAFAIL
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart-
1) need approved manual j onsite no prints could be found
2) water heater flue needs 1" clearance to combustibles in garage at ceiling
3) all R/A and supply boots need sealed
4) fireplace thimble inside exterior wall upside down doesnt meet clearance per installation instructions
5) outside air can needs insulated and sealed in attic where ties onto R/A plenum
6)R/A ducting off top of plenum needs to be secured father away from b vent in attic
7)supply wye branches need insulated in a couple places in attic bare metal showing
8) gas test failed gauge wont zero out-

left correction notice front entry window
MEC19-00733 Pressure Test2/19/20192/25/20192/25/2019 11:19:31 AMAFAIL
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- gauge wont zero out
MEC19-00524 Final2/22/20192/25/20192/25/2019 10:44:14 AMAFAIL
Call Tod with any questions. Garage code is 1234 Phone #: ###-#### Inspection requested via web by Ashley Shoecraft- flashing on exterior needs panned off and weather tight on top- flashing on top of metal siding with gap and water could run down into siding
MEC18-03709 Final2/20/20192/25/20192/25/2019 10:27:51 AMAFAIL
Inspection requested via web by Marisa Hone- need to schedule flue test to be witnessed- need right size fuses in disconnect at a/c
MEC18-04793 Final2/22/20192/25/20192/25/2019 9:57:28 AMAPASS
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- HVAC and fireplace final ok
MEC18-05653 Rough-in2/22/20192/25/20192/25/2019 9:43:53 AMAPART
locker rooms for approval for duct wrap. Jake is your contact Phone #: ###-#### Inspection requested via web by Kim Adams- locker rooms seal on duct ok- ok for insulation- call in dishwasher hood when installed
MEC19-00712 Final2/22/20192/25/20192/25/2019 9:27:07 AMAFAIL
Please call when you are on your way ###-#### Phone #: ###-#### Inspection requested via web by Andrea Grigsby- b vent needs 1" clearance to combustibles flue is against sheetrock
MEC18-02545 Final2/21/20192/25/20192/25/2019 9:04:09 AMAPASS
Inspection requested via web by Marisa Hone- a/c coil only ok
MEC18-04832 Final2/22/20192/25/20192/25/2019 8:37:35 AMAFAIL
Doris- ###-####- need to witness duct blast test none completed- air balance report needs to be onsite- fluing both units needs support and completed- condenser are not set or tied in will need uv protection on both- drains need completed both units with 1 " clearance to pvc drain piping
MEC18-04831 Final2/22/20192/25/20192/25/2019 8:35:23 AMAFAIL
Doris- ###-####- need to witness duct blast test both units- need approved manual j onsite- need air balance report- need to support fluing in garage- condenser for one unit needs completed not set and uv protection on line set- need to fix all rips and tears in arma flex in garage both units-