Inspections for the day of: Tuesday, February 5, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-00491 Final2/4/20192/5/20192/5/2019 4:08:14 PMPPASS
INSTALLER JAROD ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- furnace a/c coil co ok
MEC19-00502 Final2/4/20192/5/20192/5/2019 3:44:23 PMPFAIL
Please call the Owner Devon at ###-#### or Dan at ###-#### with a 30 minute heads up arrival time. Thank you! Phone #: ###-#### Inspection requested via web by David or K Cole- need 3 screws in all flue joints missing some and support flue- need to seal return air can and insulate to minimum R-6 above and below filter box
MEC19-00451 Final1/31/20192/5/20192/5/2019 3:06:09 PMPPASS
Please call John to ensure install is complete. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg- furnace a/c coil co ok
MEC19-00496 Pressure Test2/4/20192/5/20192/5/2019 2:43:09 PMPPART
Phone #: ###-#### Inspection requested via web by Arcadio Martinez- 20lb gas pass from meter underground to outdoor fireplace/kitchen stub in- ok to back fill underground only- need to retest whole system once gas piping is finished to fireplace- fireplaced needs permitted by whoever is installing fireplace- recall in pressure test once everything is ready
MEC19-00506 Final2/5/20192/5/20192/5/2019 2:22:33 PMPPASS
Phone #: ###-#### Inspection requested via web by Dianne Maxwell- furnace only co ok
MEC19-00494 Final2/4/20192/5/20192/5/2019 1:52:15 PMPPASS
Please call Josh prior to arrival ###-#### Inspection requested via web by Arielle Hendricks- furnace only co ok- 5lb flue test pass
MEC19-00488 Final2/4/20192/5/20192/5/2019 1:20:34 PMPPART
Please call Craig prior to arrival ###-#### Inspection requested via web by Arielle Hendricks- minisplit co ok- need electrical permit issued for condenser to final this permit out
MEC18-05653 Rough-in2/4/20192/5/20192/5/2019 10:59:53 AMAPART
for ceiling cover inspection in the kitchen/ bathroom hard lids Phone #: ###-#### Inspection requested via web by Kim Adams- insulation on supply, return and make up air in kitchen only ok- all hard lid ceilings for bathrooms and kitchen area only ok to cover- still need light test on grease duct called in when ready
MEC19-00320 Final1/31/20192/5/20192/5/2019 9:39:31 AMAPASS
Please call Art in route to inspection ###-#### Phone #: ###-#### Inspection requested via web by Justin Osterhout- furnace a/c coil co ok
MEC18-02781 Final2/4/20192/5/20192/5/2019 8:31:05 AMAPASS
815-830 am- ###-####