MEC19-00527
| Pressure Test | 2/6/2019 | 2/6/2019 | 2/6/2019 3:54:26 PM | P | PASS |
|
|
Thomas Phone #: ###-####- 20lb gas pass from meter to furnace location- tagged meter location
|
MEC18-05844
| Rough-in | 2/6/2019 | 2/6/2019 | 2/6/2019 3:20:47 PM | P | CANC |
|
|
Mike Phone #: ###-####- per phone call with mike- will reschedule
|
MEC18-05921
| Final | 2/6/2019 | 2/6/2019 | 2/6/2019 2:39:27 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- equipment installed does not match manual j- need to resubmit to city and have approved manual j onsite for final inspection
|
MEC18-05922
| Final | 2/6/2019 | 2/6/2019 | 2/6/2019 2:38:17 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by GREGORY ANDERSEN- equipment installed does not match manual j- need to resubmit to city and have approved manual j onsite for final inspection
|
MEC19-00502
| Final | 2/6/2019 | 2/6/2019 | 2/6/2019 2:36:44 PM | P | PASS |
|
|
furnace only co ok
|
MEC18-04793
| Final | 2/6/2019 | 2/6/2019 | 2/6/2019 1:59:33 PM | P | NH |
|
|
final Phone #: ###-#### Inspection requested via web by Brandon Sorensen- no access
|
MEC18-02215
| Conference | 2/6/2019 | 2/6/2019 | 2/6/2019 1:30:09 PM | P | DONE |
|
|
Need a conference for Magnificent Garden by phone today at 1:00pm if possible can contact Karl at ###-#### thank you Phone #: ###-#### Inspection requested via web by Karl Hestekin- looked at existing hoods in kitchen where walls and ceiling were replaced- wasnt on prints of any work done to kitchen area- clearance to combustibles might not be met- all labeling is gone or not ledgeable- will meet tomorrow with chad and karl at 930ish
|
MEC19-00019
| Rough-in | 2/5/2019 | 2/6/2019 | 2/6/2019 11:41:30 AM | A | FAIL |
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- fireplace flue draft stop needs minimum 1" clearance to combustibles at attic location- all exhaust fans needs sealed plastic to metal fittings(still ongoing issue)- gas line in attic needs supported /secured to structure every 10 feet to fireplace- left correction notice front entry window- furnace and coil match manual j in attic
|
MEC19-00019
| Pressure Test | 2/5/2019 | 2/6/2019 | 2/6/2019 11:36:00 AM | A | PASS |
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass- tagged meter location
|
MEC19-00515
| Rough-in | 2/5/2019 | 2/6/2019 | 2/6/2019 11:21:38 AM | A | FAIL |
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- all exhaust fans need sealed from plastic to metal fitting(still ongoing issue)- lineset in attic needs supported every 6 feet- need to insulate fresh air can where ties onto R/A plenum in attic bare metal- left correction notice front window- furnace and coil match man j in attic
|
MEC19-00515
| Pressure Test | 2/5/2019 | 2/6/2019 | 2/6/2019 11:13:05 AM | A | PASS |
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- 20lb gas pass- tagged meter location
|
MEC19-00481
| Final | 2/1/2019 | 2/6/2019 | 2/6/2019 10:18:28 AM | A | PASS |
|
|
Please call Don at ###-#### when in route Phone #: ###-#### Inspection requested via web by Sabrina DeHority- RTU final ok
|
MEC19-00503
| Final | 2/5/2019 | 2/6/2019 | 2/6/2019 9:37:14 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Scott Wickstrom- furnace only co ok
|
MEC19-00460
| Final | 1/31/2019 | 2/6/2019 | 2/6/2019 8:36:14 AM | A | CANC |
|
|
If you could call the homeowner when you''re on your way that would be greatly appreciated. Thank you Phone #: ###-#### Inspection requested via web by Kim Evans- per phone call with homeowner ionstall has not been done yet- installing next week- reschedule when install is complete
|