Inspections for the day of: Thursday, March 1, 2018.
Number of inspections: 25
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-00816 Final2/28/20183/1/20183/1/2018 4:17:08 PMPPASS
Please inspect as late as possible and call Kyle Criddle about 30 minutes prior to inspection at ###-#### so he can get home. Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace ac coil co ok
MEC18-00951 Rough-in3/1/20183/1/20183/1/2018 3:57:58 PMPFAIL
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- need approved manual J onsite for inspection- need approved nail plates on csst piping- need to finish R/I flexs not hooked up- need to seal boots to floors-
MEC18-00951 Pressure Test3/1/20183/1/20183/1/2018 3:56:29 PMPPASS
Phone #: ###-#### Inspection requested via web by Matthew BLANKENSHIP- 60lb gas pass- 20lb gas pass- 5lb pass
MEC18-00928 Rough-in3/1/20183/1/20183/1/2018 3:06:01 PMPFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak- need approved manual J onsite
MEC18-00957 Pressure Test3/1/20183/1/20183/1/2018 2:47:10 PMPPART
gas pressure witness - test gauge in basement - knock on door by garage. call me if you have access issues. Phone #: ###-#### Inspection requested via web by Dave Sorensen- 20lb gas pass- tagged meter- need to add AC to permit and pay fee by final
MEC18-00944 Final3/1/20183/1/20183/1/2018 2:30:13 PMPPASS
Please complete the inspection in the PM. Thanks. Phone #: ###-#### Inspection requested via web by Kim Lithander- ac coil co ok
MEC18-00138 Final2/28/20183/1/20183/1/2018 2:11:34 PMPPASS
Phone #: ###-#### Inspection requested via web by Randy Hart- fireplace final ok
MEC18-00137 Final2/28/20183/1/20183/1/2018 2:11:15 PMPPASS
Phone #: ###-#### Inspection requested via web by Randy Hart- final ok
MEC18-00900 Final2/26/20183/1/20183/1/2018 1:53:06 PMPPASS
Field super Chad Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney- furnace AC co ok
MEC17-02833 Final2/28/20183/1/20183/1/2018 1:25:14 PMPFAIL
Phone #: ###-#### Inspection requested via web by Dan McFate- need contractor onsite with ladder for access to roof- not sure what was installed
MEC18-00908 Final3/1/20183/1/20183/1/2018 1:09:22 PMPFAIL
Phone #: ###-#### Inspection requested via web by Devony Bullard- no one home - no access
MEC18-00917 Pressure Test3/1/20183/1/20183/1/2018 12:27:18 PMPPASS
Phone #: ###-#### Inspection requested via web by Kristin Dolan- 20lb gas pass from meter to furnace in attic- needs manual
j submitted for complete new system
MEC18-00550 Rough-in3/1/20183/1/20183/1/2018 12:15:11 PMPPASS
had to go tag gas line- all stickers were removed from window stating R/I and 20lb gas pass on it- talked to builder about this
MEC18-00813 Rough-in2/28/20183/1/20183/1/2018 11:49:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Teresa Costello- R/I ok
MEC18-00470 Pressure Test2/28/20183/1/20183/1/2018 11:24:55 AMAFAIL
If there are any questions please contact Mike C. at ###-#### Phone #: ###-#### Inspection requested via web by Stacia Haumann- guage at 54 psi- need to use 100# guage max on 60# test not 200# guage
MEC18-00719 Final2/28/20183/1/20183/1/2018 11:04:48 AMPPASS
If you could please call Bruce when heading over. Thank you! ###-#### Phone #: ###-#### Inspection requested via web by Ron Arnold- furnace co ok
MEC18-00341 Final2/28/20183/1/20183/1/2018 10:43:08 AMAPART
final - call Jeremy Phone #: ###-#### Inspection requested via web by Brandon Sorensen- ok for ceiling tiles- Roof ok- units need fired up and air balance done
MEC18-00599 Final2/27/20183/1/20183/1/2018 9:54:43 AMAPASS
can you call the customer when you are on the way. Customer just had neck surgery so she can only whisper. Thanks!! Phone #: ###-#### Inspection requested via web by Marisa Hone- furnace ac co ok
MEC18-00886 Final3/1/20183/1/20183/1/2018 9:35:06 AMPCANC
8:30-10am ###-####- schedule wrong day
MEC16-03499 Mec-Aging Inspection3/1/20183/1/20183/1/2018 9:10:08 AM PEND
contractor will schedule final per phone call
MEC17-00271 Mec-Aging Inspection3/1/20183/1/20183/1/2018 9:07:13 AM PEND
contractor will schedule final per phone call
MEC18-00925 Final2/28/20183/1/20183/1/2018 9:02:26 AMAPASS
please call ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- Furnace CO ok
MEC18-00776 Rough-in2/28/20183/1/20183/1/2018 8:50:43 AMAFAIL
Phone #: ###-#### Inspection requested via web by Jasmin Godina- need to install fiberglass piece around b vent- talked to kevin aout this by phone
MEC18-00823 Rough-in3/1/20183/1/20183/1/2018 8:49:53 AMAPASS
Phone #: ###-#### Inspection requested via web by dannyel chaloupka- R/I ok
MEC18-00775 Rough-in2/28/20183/1/20183/1/2018 8:46:53 AMAPASS
Phone #: ###-#### Inspection requested via web by Jasmin Godina- fireplace R/I ok