Inspections for the day of: Thursday, March 14, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC18-02480 Final3/8/20193/14/20193/14/2019 3:49:04 PMPPASS
Please call homeowner when you are on your way Phone #: ###-#### Inspection requested via web by Andrea Grigsby- a/c coil co ok
MEC19-01007 Final3/12/20193/14/20193/14/2019 2:23:03 PMPCANC
Phone #: ###-#### Inspection requested via web by Andrea Creek- should have been R/I inspection not final
MEC19-01007 Rough-in3/14/20193/14/20193/14/2019 2:16:33 PMPPASS
Phone #: ###-#### Inspection requested via web by Andrea Creek- need to add other to permit and pay fee for R/A and supply ducting thats installed by final- need to seal supply duct in basement and insulate bare metal in garage for supply and R/A ducting installed and attic by final- toe kick will need ducted all the way out under cabinet to register by final- R/I ok for 2 bath fans, 1 dryer exhaust and range hood ducting
MEC19-00971 Final3/14/20193/14/20193/14/2019 1:20:28 PMPPART
Call if door is locked // Travis Phone #: ###-####- need to secure all new gas piping to new supports on roof- temp occupancy ok-
MEC19-00874 Final3/13/20193/14/20193/14/2019 11:41:06 AMAPASS
PLEASE CALL HOMEOWNER JASON WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace only co ok
MEC18-05653 Final3/13/20193/14/20193/14/2019 11:17:56 AMAPART
I need a final, temp c of o in the kitchen and rough in inspection in the locker rooms. Jake is your contact.
Thanks
Phone #: ###-#### Inspection requested via web by Kim Adams- need to extend flues on 2 units on roof 3 feet above intake- need 1500 degree gasket on both class 1hood exhaust fans- need to pan off 2 transfers above ceiling to kitchen- need all equipment set under both class 1 hoods and class 2 hood needs dishwasher installed in center- need air balance report for both class 1 hoods and 1 class 2 hood and MAU- R/I in locker rooms ok- ok to cover- 2 ceiling heaters NW entry ok- storage room in kitchen area ok to cover
MEC19-01023 Final3/14/20193/14/20193/14/2019 9:48:52 AMAPASS
Final inspection ; Eric is the contact Phone #: ###-#### Inspection requested via web by Kim Adams- final ok 2 head split and condenser on roof- supply and transfer ok
MEC19-00762 Rough-in3/13/20193/14/20193/14/2019 8:56:56 AMAFAIL
Phone #: ###-#### Inspection requested via web by Debbie Marino- need approved man j onsite- need installation instructions readily accessable on fireplace- fireplace clearance to fluing combustibles need addressed- all arma flex needs all rips and tears fixed and 2 wire needs clearance to flue piping in attic
MEC19-00762 Pressure Test3/13/20193/14/20193/14/2019 8:54:00 AMAFAIL
Phone #: ###-#### Inspection requested via web by Debbie Marino- gauge at 5 psi
MEC19-00966 Final3/11/20193/14/20193/14/2019 8:34:50 AMAPASS
Homeowner Clancy O''Heffernan ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace only co ok
MEC18-02884 Mec-Aging Inspection3/14/20193/14/20193/14/2019 8:01:20 AM CANC
contractor needs to reschedule inspection