MEC18-02480
| Final | 3/8/2019 | 3/14/2019 | 3/14/2019 3:49:04 PM | P | PASS |
|
|
Please call homeowner when you are on your way Phone #: ###-#### Inspection requested via web by Andrea Grigsby- a/c coil co ok
|
MEC19-01007
| Final | 3/12/2019 | 3/14/2019 | 3/14/2019 2:23:03 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek- should have been R/I inspection not final
|
MEC19-01007
| Rough-in | 3/14/2019 | 3/14/2019 | 3/14/2019 2:16:33 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Andrea Creek- need to add other to permit and pay fee for R/A and supply ducting thats installed by final- need to seal supply duct in basement and insulate bare metal in garage for supply and R/A ducting installed and attic by final- toe kick will need ducted all the way out under cabinet to register by final- R/I ok for 2 bath fans, 1 dryer exhaust and range hood ducting
|
MEC19-00971
| Final | 3/14/2019 | 3/14/2019 | 3/14/2019 1:20:28 PM | P | PART |
|
|
Call if door is locked // Travis Phone #: ###-####- need to secure all new gas piping to new supports on roof- temp occupancy ok-
|
MEC19-00874
| Final | 3/13/2019 | 3/14/2019 | 3/14/2019 11:41:06 AM | A | PASS |
|
|
PLEASE CALL HOMEOWNER JASON WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery- furnace only co ok
|
MEC18-05653
| Final | 3/13/2019 | 3/14/2019 | 3/14/2019 11:17:56 AM | A | PART |
|
|
I need a final, temp c of o in the kitchen and rough in inspection in the locker rooms. Jake is your contact. Thanks Phone #: ###-#### Inspection requested via web by Kim Adams- need to extend flues on 2 units on roof 3 feet above intake- need 1500 degree gasket on both class 1hood exhaust fans- need to pan off 2 transfers above ceiling to kitchen- need all equipment set under both class 1 hoods and class 2 hood needs dishwasher installed in center- need air balance report for both class 1 hoods and 1 class 2 hood and MAU- R/I in locker rooms ok- ok to cover- 2 ceiling heaters NW entry ok- storage room in kitchen area ok to cover
|
MEC19-01023
| Final | 3/14/2019 | 3/14/2019 | 3/14/2019 9:48:52 AM | A | PASS |
|
|
Final inspection ; Eric is the contact Phone #: ###-#### Inspection requested via web by Kim Adams- final ok 2 head split and condenser on roof- supply and transfer ok
|
MEC19-00762
| Rough-in | 3/13/2019 | 3/14/2019 | 3/14/2019 8:56:56 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- need approved man j onsite- need installation instructions readily accessable on fireplace- fireplace clearance to fluing combustibles need addressed- all arma flex needs all rips and tears fixed and 2 wire needs clearance to flue piping in attic
|
MEC19-00762
| Pressure Test | 3/13/2019 | 3/14/2019 | 3/14/2019 8:54:00 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Debbie Marino- gauge at 5 psi
|
MEC19-00966
| Final | 3/11/2019 | 3/14/2019 | 3/14/2019 8:34:50 AM | A | PASS |
|
|
Homeowner Clancy O''Heffernan ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace only co ok
|
MEC18-02884
| Mec-Aging Inspection | 3/14/2019 | 3/14/2019 | 3/14/2019 8:01:20 AM | | CANC |
|
|
contractor needs to reschedule inspection
|